Configuration of the Xanbus AGS
When the AGS Home Screen is first displayed, the menu defaults to the
GenMode Menu. If configuration changes need to be made, the
Configuration Menu can be accessed by pressing the Enter, Up arrow, and
Down arrow buttons all at same time to access the Advanced Settings.
AC In/Charge | XAGS 00: Setup | STBY/ON |
| |
Inverter On |
| |||
GenMode | [ManualOff] | Fault Clear |
| |
Low Battery | Mode | [Operating] | Xanbus AGS Menu | |
Fault | Clear Faults Warnings | |||
View Device Info |
|
| ||
|
|
| XAGS 00: Setup | |
|
|
| Advanced Settings | |
|
|
| GenMode | [ManualOff] |
| Enter | Func | Clear Faults Warnings | |
|
|
| View Device Info | |
Xanbus System Control Panel (SCP) |
| FGA: |
| |
|
|
| XAGS 00: Setup | |
|
| To access the Advanced Settings menu, |
| |
|
| Press Enter and Up and Down arrows together Advanced Settings | ||
|
|
| GenMode | [ManualOff] |
Clear Faults Warnings
View Device Info
XAGS 00: Config
QT EN | [Enabled] |
|
| |
QT Begin | [9:00PM] |
|
| |
QT End | [8:00AM] |
|
| |
Gen Type | [2] |
|
| |
Cfg Trigger |
|
|
| |
|
|
| ||
Cfg Gen |
|
|
|
|
Restore Defaults
To change configuration parameters...
Press Enter to move forward into the Config menu.
XAGS 00: Triggers
Start DCV 30 Sec | [40.0V] |
Start DCV 15 Sec | [Disabled] |
Start DCV 2 hr | [Disabled] |
Start DCV 24 Hr | [Disabled] |
Stop Float | [Disabled] |
Stop Absorb | [Disabled] |
StopV | [Disabled] |
Temp1 | [Disabled] |
Temp2 | [Disabled] |
Load | [Disabled] |
Start Load | [15A] |
Stop Load | [10A] |
XAGS 00: Gen |
|
Starter Cool Down | [60sec] |
Gen Cool Down | [30sec] |
Gen Spin Down | [3sec] |
Max Runtime | [4hours] |
Exercise per | [21days] |
Exercise Dur | [30min] |
Exercise Time | [9:00AM] |
Relay 3 | [Not Used] |
Gen Run Hold Time | [0.5s] |
Crank Delay | [1sec] |
Crank Time | [30sec] |
Use these buttons to change the settings.
Press ENTER to accept the new setting.
To return to the B asic Settings menu,
Press Enter and Up and Down arrows together
Use these buttons to select the desired menu.
Press ENTER to move the cursor to the changeable settings.
Press Func to return to the Xanbus AGS Home screen.
Crank Retry Time | [40sec] |
| |
Preheat Time | [0sec] |
| |
Gen Start Tries | [3] |
| |
|
|
|
|
XAGS 00: Gen |
|
| |
Dev Name | [AGS] |
| |
Dev Number | [00] |
| |
Connections |
|
|
|
|
|
|
|
XAGS 00: Conn
DC Conn | [HouseBatt1] |
AC In | [Grid1] |
AC Out | [ACLoad] |
Generator | [Gen1] |
Figure 32 AGS Configuration Menu Contents
39 |