Configuration of the Xanbus AGS
Cfg Gen
The "Cfg Gen" menu provides the means to customize the following settings if the generator being used doesn’t conform to one of the preset generator types or if an exercise period needs to be scheduled.
The Generator Configuration menu contains the following items:
•"Starter Cool Down"
•"Gen Cool Down"
•"Gen Spin Down"
•"Max Run Time"
•"Exercise Per"
•"Exercise Dur"
•"Exercise Time"
•"Relay3"
•"Gen Run Hold Time"
•"Crank Delay"
•"Crank Time"
•"Crank Retry Time"
•"Preheat Time"
•"Gen Start Tries"
Starter Cool Down
Purpose The Starter Cool Down setting allows an interval to be set between start attempts if the generator fails to start on the first attempt. This time period allows the start motor to cool sufficiently before the AGS signals it to begin cranking again.
Values | Default |
|
|
1s to 250s (increments of 1s) | 60s |
|
|
When to use This setting is automatically configured when a "Gen Type" is selected for the generator. Customize the "Starter Cool Down" trigger on the advice of the generator manufacturer or authorized service personnel.
53 |