Xanbus Automatic Generator Start Installation
Type 7
Type 7 will work with both
AGS Harness W ires |
| Generator W ires | |
| 12 |
| GENERATOR RUN SIGNAL |
| 13 |
| GENERATOR RUN SIGNAL RETURN |
Relay 1 | 14 | 5A fuse | RUN |
16 |
|
| |
|
|
|
For additional information, see “Circuit Limitations” on page 11.
Figure 13 Type 7 Connection Diagram (two-wire)
AGS Harness W ires | Generator W ires |
Relay Function | Preset Configuration Setting |
|
|
Relay 1 mode | Run |
Relay 3 mode | No function |
Gen Run signal hold time | 0.5 s |
Preheat time | 20 s |
Preheat to crank delay | 1 s |
Crank time | 15 s |
Crank retry time | 30 s |
Gen Cool Down | 30 s |
Gen Spin Down | 3 s |
Shutdown bypass time | 0 s |
Start tries | 3 |
|
|
Relay 1
12
13
14
16
|
|
|
| GENERATOR RUN SIGNAL |
|
|
|
| |
|
|
|
| GENERATOR RUN SIGNAL RETURN |
|
|
| 5A fuse | |
|
|
| RUN | |
|
|
| ||
|
| |||
|
|
| ||
|
|
|
|
|
Relay 2
17
18
5A fuse | START |
For additional information, see “Circuit Limitations” on page 11.
Figure 14 Type 7 Connection Diagram (three-wire)
| 21 |