Xantrex Technology 809-0915 manual Stop Load

Page 62

Configuration of the Xanbus AGS

Stop Load

Full name Stop on Inverter Load Current

Purpose The "Stop Load" trigger enables the AGS to stop the generator when the AC load falls below a specific level for 1 minute. The "Stop Load" setting applies to situations when the AGS has started the generator to assist the inverter with powering the AC load.

Dependencies The "Stop Load" trigger requires the AGS to be in Automatic mode and the "Load" trigger to be set to [Enabled]. It also needs to have a value starting value set in the "Start Load" trigger.

Values

Default

 

 

7.0 A to 28.0 A (increments of 1 A)

7.0 A

 

 

52

Xanbus Automatic Generator Start (AGS) Owner’s Guide

Image 62
Contents Xanbus Automatic Generator Start AGS Page Date and Revision TrademarksExclusion for Documentation Document Part NumberScope About This GuidePurpose AudienceRelated Information Important Safety Instructions ReferenceFCC Information to the User Restrictions on USEPage Contents Page Introduction Xanbus Automatic Generator Start AGS Basic FunctionSystem Requirements Functions Material List AGS unitXanbus-Enabled Products and Accessories Features Front panel featuresBottom panel features XanbusChoosing a Location Xanbus Automatic Generator Start InstallationMaterials and Tools Required Routing Connections Shock and Energy HazardsInstallation Overview Mounting the UnitWiring to the 20-contact Connector Circuit Parameter Circuit MaximumTo install the AGS using the wiring harness Ft m Over 30 ft mXanbus Automatic Generator Start Installation Connecting the Generator Relay Function Preset Configuration Setting TypeType 2 Connection Diagram Type 3 Connection Diagram Type 4 Connection Diagram Type 5 Connection Diagram Relay FunctionType 6 Connection Diagram Type 7 Connection Diagram two-wire Type 8 Connection Diagram two-wire Type 9 Connection Diagram Type 10 Connection Diagram Type 11 Connection Diagram Type 12 Connection Diagram Type 13 Connection Diagram Type 14 Connection Diagram two-wire Number Function Wire Color Connecting the Thermostats optionalWire Connecting an External Manual ON/OFF Switch optional Connecting an External Shutdown optionalConnecting an External ON/OFF LED Wire Wiring Harness Number Function Wire ColorExternal ON/OFF Switch and LED Wiring Diagram Connecting the Wiring Harness to the AGS To connect the wiring harness to the AGSConnecting the AGS to the Xanbus Network Verifying Power Is Available Connecting the Xanbus System Control Panel SCPConfiguration of the Xanbus AGS OverviewAccessing the AGS Menu To change operational settings on the AGS MenuXanbus AGS Menu To configure Xanbus Automatic Generator Start AGS MenuAGS Configuration Menu Contents Value Description Configuration MenuQT En QT Begin QT End Gen TypeDescription Cfg Trigger Values Default Start DCV 30 secStart DCV 15 min Start DCV 2 hr Start DCV 24 hrStop Float Stop AbsorbStop Temp1 Temp2Start Load Value DefaultLoad Stop Load Cfg Gen Starter Cool DownGen Cool Down Gen Spin DownMax Run Time Exercise PerExercise Dur Exercise TimeRelay3 Gen Run Hold TimeCrank Retry Time Crank DelayCrank Time Preheat TimeGen Start Tries GenMode Restore DefaultsAutomatic Mode Manual On Mode Manual Off ModeView Device Info View Fault LogMode View Event LogUser Settings ItemsAccessing the AGS Home Screen Operation of the Xanbus AGSStarting and Stopping the Generator To start the generator manuallyUsing Quiet Time To enable Quiet TimePutting the AGS in Standby Mode Modes of OperationReturning the AGS to Operating Mode To return the AGS to Operating ModeTroubleshooting To view a message from a fault list or warning listTroubleshooting AGS Warning Messages Fault Reference Table AGS Fault MessagesEnvironmental Specifications SpecificationsElectrical Specifications Regulatory ApprovalsPhysical Specifications Dimensions Weight Mounting ConnectorsWarranty and Return Information WarrantyWarranty and Return Information DisclaimerReturn Material Authorization Policy Return ProcedureInformation About Your System Generator Starting Types Recommended FeaturesAppendix a Generator Auto Start Requirements and Types Two Wire Three-Wire OnanThree-Wire Automotive Appendix B Relay Timing RunModeMomentaryRun Mode MomentaryRun Mode Timing DiagramGlowStop Mode GlowStop Mode Timing DiagramStartStop Mode StartStop Mode Timing DiagramPulseStop Mode PulseStop Mode Timing DiagramPulseStop Mode Relay 1 Behavior Page Page Xantrex Technology USA Inc