Xantrex Technology 809-0915 manual Temp1, Temp2

Page 60

Configuration of the Xanbus AGS

Temp1

Full name Thermostat 1

Purpose The "Temp1" trigger enables the generator to start in response to a signal from a thermostat. With "Temp1" set to [Enabled], the AGS will start the generator to help power the item controlled by that thermostat.

Temp2

Full name Thermostat 2

Purpose "Temp2" is intended to be used when the AGS is connected to a second thermostat. All information and procedures for "Temp1" also apply for "Temp2".

Values

Default

 

Values

Default

 

 

 

 

 

Disabled, Enabled

Disabled

 

Disabled, Enabled

Disabled

 

 

 

 

 

When to use Enable "Temp1" if a thermostat is available that controls a component that has a high-power requirement such as a furnace or an air conditioning system.

Considerations If "Temp1" is enabled, the generator will start in response to a signal from the thermostat. Everything related to setting the thermostat must be done on the thermostat. For example: setting the temperature at which the furnace or air conditioning system comes on must be done on the thermostat. There are no thermostat temperature settings on the AGS or the Xanbus System Control Panel (SCP).

If "Temp1" is disabled, the component connected to that thermostat will require that the generator be started manually in order for that component to have power. Otherwise, the component will need to be connected to another AC input source.

50

Xanbus Automatic Generator Start (AGS) Owner’s Guide

Image 60
Contents Xanbus Automatic Generator Start AGS Page Trademarks Exclusion for DocumentationDate and Revision Document Part NumberAbout This Guide PurposeScope AudienceRelated Information Important Safety Instructions ReferenceFCC Information to the User Restrictions on USEPage Contents Page Introduction Xanbus Automatic Generator Start AGS Basic FunctionSystem Requirements Functions Material List AGS unitXanbus-Enabled Products and Accessories Features Front panel featuresBottom panel features XanbusXanbus Automatic Generator Start Installation Materials and Tools RequiredChoosing a Location Routing Connections Shock and Energy HazardsInstallation Overview Mounting the UnitWiring to the 20-contact Connector Circuit Parameter Circuit MaximumTo install the AGS using the wiring harness Ft m Over 30 ft mXanbus Automatic Generator Start Installation Connecting the Generator Relay Function Preset Configuration Setting TypeType 2 Connection Diagram Type 3 Connection Diagram Type 4 Connection Diagram Type 5 Connection Diagram Relay FunctionType 6 Connection Diagram Type 7 Connection Diagram two-wire Type 8 Connection Diagram two-wire Type 9 Connection Diagram Type 10 Connection Diagram Type 11 Connection Diagram Type 12 Connection Diagram Type 13 Connection Diagram Type 14 Connection Diagram two-wire Connecting the Thermostats optional WireNumber Function Wire Color Connecting an External Manual ON/OFF Switch optional Connecting an External Shutdown optionalConnecting an External ON/OFF LED Wire Wiring Harness Number Function Wire ColorExternal ON/OFF Switch and LED Wiring Diagram Connecting the Wiring Harness to the AGS To connect the wiring harness to the AGSConnecting the AGS to the Xanbus Network Verifying Power Is Available Connecting the Xanbus System Control Panel SCPConfiguration of the Xanbus AGS OverviewAccessing the AGS Menu To change operational settings on the AGS MenuXanbus AGS Menu To configure Xanbus Automatic Generator Start AGS MenuAGS Configuration Menu Contents Configuration Menu QT EnValue Description QT Begin QT End Gen TypeDescription Cfg Trigger Values Default Start DCV 30 secStart DCV 15 min Start DCV 2 hr Start DCV 24 hrStop Float Stop AbsorbStop Temp1 Temp2Value Default LoadStart Load Stop Load Cfg Gen Starter Cool DownGen Cool Down Gen Spin DownMax Run Time Exercise PerExercise Dur Exercise TimeRelay3 Gen Run Hold TimeCrank Delay Crank TimeCrank Retry Time Preheat TimeGen Start Tries Restore Defaults Automatic ModeGenMode Manual On Mode Manual Off ModeView Fault Log ModeView Device Info View Event LogUser Settings ItemsAccessing the AGS Home Screen Operation of the Xanbus AGSStarting and Stopping the Generator To start the generator manuallyUsing Quiet Time To enable Quiet TimePutting the AGS in Standby Mode Modes of OperationReturning the AGS to Operating Mode To return the AGS to Operating ModeTroubleshooting To view a message from a fault list or warning listTroubleshooting AGS Warning Messages Fault Reference Table AGS Fault MessagesSpecifications Electrical SpecificationsEnvironmental Specifications Regulatory ApprovalsPhysical Specifications Dimensions Weight Mounting ConnectorsWarranty and Return Information WarrantyWarranty and Return Information DisclaimerReturn Material Authorization Policy Return ProcedureInformation About Your System Recommended Features Appendix a Generator Auto Start Requirements and TypesGenerator Starting Types Two Wire Three-Wire OnanThree-Wire Automotive Appendix B Relay Timing RunModeMomentaryRun Mode MomentaryRun Mode Timing DiagramGlowStop Mode GlowStop Mode Timing DiagramStartStop Mode StartStop Mode Timing DiagramPulseStop Mode PulseStop Mode Timing DiagramPulseStop Mode Relay 1 Behavior Page Page Xantrex Technology USA Inc