Xantrex Technology 809-0915 manual Gen Cool Down, Gen Spin Down

Page 64

Configuration of the Xanbus AGS

Gen Cool Down

Purpose The Gen Cool Down setting allows an interval to be set between a generator stop trigger occurring and the AGS actually stopping the generator. This setting is used in Freedom SW system to unload the generator before the AGS shuts it down. When a stop trigger occurs, the AGS enters a Generator cool down state where it continues to run the generator for the specified time period. At the same time the Freedom SW Series Inverter/Charger will disconnect the generator when it detects the AGS in Generator Cool Down, allowing the generator operate unloaded and cool down before it is shut down.

This helps improves reliability of the generator by reducing temperature peaking due to abrupt shut down of a loaded generator. It also reduces the probability of the generator backfiring that typically happens when the generator is abruptly shutdown while under heavy load. Gen Cool Down applies to all stop triggers namely Stop V, Stop Load, Stop Float, Stop Absorb, Stop Load, and Manual Off.

Values

Default

 

 

1s to 90s (increments of 1s)

30s

 

 

When to use This setting is automatically configured when a “Gen Type” is selected for the generator. Customize the “Gen Cool Down” trigger on the advice of the generator manufacturer or authorized service personnel.

Gen Spin Down

Purpose The Gen Spin Down setting allows an interval to be set between a generator stop signal being sent at the end of a Gen Cool Down cycle and the AGS changing the Generator State to “stopped.” This setting is used in the Freedom SW System to allow the generator to completely stop, thereby reducing its output voltage to zero and pulling the B+ signal low before the Freedom SW Series Inverter/Charger can qualify and transfer AC power.

This helps the system operate properly in cases where the generator does not immediately stop when the stop signal is sent to the AGS. Gen Spin Down applies to all stop triggers—Stop V, Stop Load, Stop Float, Stop Absorb, Stop Load, and Manual Off.

Values

Default

 

 

1s to 900s (increments of 1s)

3s

 

 

When to use This setting is automatically configured when a “Gen Type” is selected for the generator. Customize the “Gen Spin Down” trigger on the advice of the generator manufacturer or authorized service personnel.

54

Xanbus Automatic Generator Start (AGS) Owner’s Guide

Image 64
Contents Xanbus Automatic Generator Start AGS Page Trademarks Exclusion for DocumentationDate and Revision Document Part NumberAbout This Guide PurposeScope AudienceRelated Information Important Safety Instructions ReferenceFCC Information to the User Restrictions on USEPage Contents Page Introduction Xanbus Automatic Generator Start AGS Basic FunctionSystem Requirements Functions Material List AGS unitXanbus-Enabled Products and Accessories Features Front panel featuresBottom panel features XanbusMaterials and Tools Required Xanbus Automatic Generator Start InstallationChoosing a Location Routing Connections Shock and Energy HazardsInstallation Overview Mounting the UnitWiring to the 20-contact Connector Circuit Parameter Circuit MaximumTo install the AGS using the wiring harness Ft m Over 30 ft mXanbus Automatic Generator Start Installation Connecting the Generator Relay Function Preset Configuration Setting TypeType 2 Connection Diagram Type 3 Connection Diagram Type 4 Connection Diagram Type 5 Connection Diagram Relay FunctionType 6 Connection Diagram Type 7 Connection Diagram two-wire Type 8 Connection Diagram two-wire Type 9 Connection Diagram Type 10 Connection Diagram Type 11 Connection Diagram Type 12 Connection Diagram Type 13 Connection Diagram Type 14 Connection Diagram two-wire Wire Connecting the Thermostats optionalNumber Function Wire Color Connecting an External Manual ON/OFF Switch optional Connecting an External Shutdown optionalConnecting an External ON/OFF LED Wire Wiring Harness Number Function Wire ColorExternal ON/OFF Switch and LED Wiring Diagram Connecting the Wiring Harness to the AGS To connect the wiring harness to the AGSConnecting the AGS to the Xanbus Network Verifying Power Is Available Connecting the Xanbus System Control Panel SCPConfiguration of the Xanbus AGS OverviewAccessing the AGS Menu To change operational settings on the AGS MenuXanbus AGS Menu To configure Xanbus Automatic Generator Start AGS MenuAGS Configuration Menu Contents QT En Configuration MenuValue Description QT Begin QT End Gen TypeDescription Cfg Trigger Values Default Start DCV 30 secStart DCV 15 min Start DCV 2 hr Start DCV 24 hrStop Float Stop AbsorbStop Temp1 Temp2Load Value DefaultStart Load Stop Load Cfg Gen Starter Cool DownGen Cool Down Gen Spin DownMax Run Time Exercise PerExercise Dur Exercise TimeRelay3 Gen Run Hold TimeCrank Delay Crank TimeCrank Retry Time Preheat TimeGen Start Tries Automatic Mode Restore DefaultsGenMode Manual On Mode Manual Off ModeView Fault Log ModeView Device Info View Event LogUser Settings ItemsAccessing the AGS Home Screen Operation of the Xanbus AGSStarting and Stopping the Generator To start the generator manuallyUsing Quiet Time To enable Quiet TimePutting the AGS in Standby Mode Modes of OperationReturning the AGS to Operating Mode To return the AGS to Operating ModeTroubleshooting To view a message from a fault list or warning listTroubleshooting AGS Warning Messages Fault Reference Table AGS Fault MessagesSpecifications Electrical SpecificationsEnvironmental Specifications Regulatory ApprovalsPhysical Specifications Dimensions Weight Mounting ConnectorsWarranty and Return Information WarrantyWarranty and Return Information DisclaimerReturn Material Authorization Policy Return ProcedureInformation About Your System Appendix a Generator Auto Start Requirements and Types Recommended FeaturesGenerator Starting Types Two Wire Three-Wire OnanThree-Wire Automotive Appendix B Relay Timing RunModeMomentaryRun Mode MomentaryRun Mode Timing DiagramGlowStop Mode GlowStop Mode Timing DiagramStartStop Mode StartStop Mode Timing DiagramPulseStop Mode PulseStop Mode Timing DiagramPulseStop Mode Relay 1 Behavior Page Page Xantrex Technology USA Inc