Xantrex Technology 809-0915 manual Type 14 Connection Diagram two-wire

Page 38

Xanbus Automatic Generator Start Installation

Type 14

Type 14 works with two-wire generators that use an integrated engine control module to perform the necessary relay cycles to start and stop the generator. This is similar to Type 8 but without the B+ signal requirement. The AGS closes relay 1 to start the generator and illuminates the Generator On light to indicate the relay is closed. To stop the generator, relay 1 is opened and the Generator On light turned off.

IMPORTANT: Since Type 14 does not monitor the generator run status, illumination of the Generator On light on the AGS does not necessarily indicate the generator is actually running. If this generator type is used, ensure the generator’s integrated controller has the ability to monitor, control and report generator status and faults. With Type 14, no faults are raised if the generator fails to start or stop or is externally started or stopped.

Once the generator is stopped, there is a 10-minute delay before the generator can be re-started using the AGS. This is to allow the generator’s integrated engine controller to completely and safely shut down the generator. This delay can be adjusted by changing the Gen Spin down setting.

AGS Harness Wires

 

Generator Wires

Relay 1

14

5A fuse

RUN

16

 

RELAY 1 RETURN

 

 

For additional information, see “Circuit Limitations” on page 11.

Figure 22 Type 14 Connection Diagram (two-wire)

Relay Function

Preset Configuration Setting

 

 

Relay 1 mode

RunStop

Relay 3 mode

Not used

Gen Run signal hold time

0 s

Preheat time

0 s

Preheat to crank delay

0 s

Crank time

0 s

Crank retry time

0 s

Gen Cool Down

30 s

Gen Spin Down

600 s

Shutdown bypass time

0 s

Start tries

1

28

Xanbus Automatic Generator Start (AGS) Owner’s Guide

Image 38
Contents Xanbus Automatic Generator Start AGS Page Date and Revision TrademarksExclusion for Documentation Document Part NumberScope About This GuidePurpose AudienceRelated Information Important Safety Instructions ReferenceFCC Information to the User Restrictions on USEPage Contents Page Introduction Xanbus Automatic Generator Start AGS Basic FunctionSystem Requirements Functions Material List AGS unitXanbus-Enabled Products and Accessories Features Front panel featuresBottom panel features XanbusChoosing a Location Xanbus Automatic Generator Start InstallationMaterials and Tools Required Routing Connections Shock and Energy HazardsInstallation Overview Mounting the UnitWiring to the 20-contact Connector Circuit Parameter Circuit MaximumTo install the AGS using the wiring harness Ft m Over 30 ft mXanbus Automatic Generator Start Installation Connecting the Generator Relay Function Preset Configuration Setting TypeType 2 Connection Diagram Type 3 Connection Diagram Type 4 Connection Diagram Type 5 Connection Diagram Relay FunctionType 6 Connection Diagram Type 7 Connection Diagram two-wire Type 8 Connection Diagram two-wire Type 9 Connection Diagram Type 10 Connection Diagram Type 11 Connection Diagram Type 12 Connection Diagram Type 13 Connection Diagram Type 14 Connection Diagram two-wire Number Function Wire Color Connecting the Thermostats optionalWire Connecting an External Manual ON/OFF Switch optional Connecting an External Shutdown optionalConnecting an External ON/OFF LED Wire Wiring Harness Number Function Wire ColorExternal ON/OFF Switch and LED Wiring Diagram Connecting the Wiring Harness to the AGS To connect the wiring harness to the AGSConnecting the AGS to the Xanbus Network Verifying Power Is Available Connecting the Xanbus System Control Panel SCPConfiguration of the Xanbus AGS OverviewAccessing the AGS Menu To change operational settings on the AGS MenuXanbus AGS Menu To configure Xanbus Automatic Generator Start AGS MenuAGS Configuration Menu Contents Value Description Configuration MenuQT En QT Begin QT End Gen TypeDescription Cfg Trigger Values Default Start DCV 30 secStart DCV 15 min Start DCV 2 hr Start DCV 24 hrStop Float Stop AbsorbStop Temp1 Temp2Start Load Value DefaultLoad Stop Load Cfg Gen Starter Cool DownGen Cool Down Gen Spin DownMax Run Time Exercise PerExercise Dur Exercise TimeRelay3 Gen Run Hold TimeCrank Retry Time Crank DelayCrank Time Preheat TimeGen Start Tries GenMode Restore DefaultsAutomatic Mode Manual On Mode Manual Off ModeView Device Info View Fault LogMode View Event LogUser Settings ItemsAccessing the AGS Home Screen Operation of the Xanbus AGSStarting and Stopping the Generator To start the generator manuallyUsing Quiet Time To enable Quiet TimePutting the AGS in Standby Mode Modes of OperationReturning the AGS to Operating Mode To return the AGS to Operating ModeTroubleshooting To view a message from a fault list or warning listTroubleshooting AGS Warning Messages Fault Reference Table AGS Fault MessagesEnvironmental Specifications SpecificationsElectrical Specifications Regulatory ApprovalsPhysical Specifications Dimensions Weight Mounting ConnectorsWarranty and Return Information WarrantyWarranty and Return Information DisclaimerReturn Material Authorization Policy Return ProcedureInformation About Your System Generator Starting Types Recommended FeaturesAppendix a Generator Auto Start Requirements and Types Two Wire Three-Wire OnanThree-Wire Automotive Appendix B Relay Timing RunModeMomentaryRun Mode MomentaryRun Mode Timing DiagramGlowStop Mode GlowStop Mode Timing DiagramStartStop Mode StartStop Mode Timing DiagramPulseStop Mode PulseStop Mode Timing DiagramPulseStop Mode Relay 1 Behavior Page Page Xantrex Technology USA Inc