Configuration of the Xanbus AGS
Mode
The "Mode" menu item is a device operating mode and provides the means to put the AGS in Standby Mode or return it from to Operating Mode.
The AGS Mode must be set to [Standby] before selecting a generator type. Selecting Standby stops the generator (if it is running).
While in Standby, the AGS “listens” to and reports its status to the network. It will not start the generator manual or automatically while in Standby.
View Event Log
Purpose The Event Log displays the last 20 AGS events for reference. Events can include:
•Starting and stopping the generator.
•Trigger events. See table below for a detailed list of trigger events.
•Changing the system mode.
•Changing the system clock.
•Commands to restore the default settings.
View Device Info
The "View Device Info" menu provides a means to view the Fault, Warning and Event logs. It is also where the settings can be restored to factory default settings.
View Fault Log
Purpose The Fault Log displays the last 20 AGS faults for reference to assist the user in troubleshooting problems.
When to use Consult the Fault Log when troubleshooting or before seeking technical assistance.
View Warning Log
Purpose The Warning Log displays the last 20 AGS warnings for reference.
When to use Consult the Warning Log when troubleshooting or before seeking technical assistance.
Event |
|
Displayed | Description of Event Trigger |
|
|
NotOn | Generator is not running |
LowBattV | Preset minimum battery voltage with associated time |
| delay |
CntctClosed | Activated thermostat 1 or 2 |
ACIHigh | Preset maximum inverter load current |
Exercise | Preset exercise period, exercise time, and exercise |
| duration |
ManualOn | Started manually using System Control Panel |
ExtOnviaAGS | Started by external switch connected to AGS |
ExtOnviaGen | Started by switch connected to generator |
UnableToStop | AGS has lost control of the running generator |
|
|
62 | Xanbus Automatic Generator Start (AGS) Owner’s Guide |