Appendix B: Relay Timing

StartStop Mode

 

 

For generators with StartStop mode starting types (Types 4, 5, 9, 10):

The “Delay” refers to the “Preheat to Crank Delay” and may be zero.

Relay 1 (Stop) and Relay 2 (Start) can be used with a common ground

Cranking will cease when the generator run signal goes high for the

 

for three-wire configured generators.

 

specified hold time or when the crank time has elapsed.

If Relay 3 is configured for preheat, the signal only shows up on Relay

To get the ShutDown Bypass on Relay 3 with no preheat, Relay 3 must

 

3.

 

be configured for Preheat with ShutDown Bypass and have the Preheat

The Preheat on Relay 3 will not overlap the Crank Time if ShutDown

 

time set to zero.

 

Bypass is not enabled.

StartStop mode is essentially the same as GlowStop mode with no

If the ShutDown Bypass is enabled, the Preheat on Relay 3 will remain

 

preheat on Relay 1.

 

high for the Crank Time and for the ShutDown Bypass period after

 

 

 

cranking.

 

 

Stop

Relay 1: Stop

 

 

 

Delay

 

Start

Shutdown

 

 

 

 

 

Relay 2: Start (Cranking)

 

 

Crank

Bypass

 

 

 

 

 

Time

 

 

 

 

 

 

 

 

 

 

 

 

Relay 3: Preheat (Glow)

Preheat

 

 

 

 

 

 

 

 

 

 

& Shutdown Bypass

 

 

 

 

 

Figure 40 StartStop Mode Timing Diagram

 

 

975-0082-01-01

85

Image 95
Contents Xanbus Automatic Generator Start AGS Page Document Part Number TrademarksExclusion for Documentation Date and RevisionAudience About This GuidePurpose ScopeRelated Information Reference Important Safety InstructionsRestrictions on USE FCC Information to the UserPage Contents Page Xanbus Automatic Generator Start AGS Basic Function IntroductionSystem Requirements Functions AGS unit Material ListXanbus-Enabled Products and Accessories Front panel features FeaturesXanbus Bottom panel featuresChoosing a Location Xanbus Automatic Generator Start InstallationMaterials and Tools Required Shock and Energy Hazards Routing ConnectionsMounting the Unit Installation OverviewCircuit Parameter Circuit Maximum Wiring to the 20-contact ConnectorFt m Over 30 ft m To install the AGS using the wiring harnessXanbus Automatic Generator Start Installation Connecting the Generator Type Relay Function Preset Configuration SettingType 2 Connection Diagram Type 3 Connection Diagram Type 4 Connection Diagram Relay Function Type 5 Connection DiagramType 6 Connection Diagram Type 7 Connection Diagram two-wire Type 8 Connection Diagram two-wire Type 9 Connection Diagram Type 10 Connection Diagram Type 11 Connection Diagram Type 12 Connection Diagram Type 13 Connection Diagram Type 14 Connection Diagram two-wire Number Function Wire Color Connecting the Thermostats optionalWire Connecting an External Shutdown optional Connecting an External Manual ON/OFF Switch optionalWire Wiring Harness Number Function Wire Color Connecting an External ON/OFF LEDExternal ON/OFF Switch and LED Wiring Diagram To connect the wiring harness to the AGS Connecting the Wiring Harness to the AGSConnecting the AGS to the Xanbus Network Connecting the Xanbus System Control Panel SCP Verifying Power Is AvailableOverview Configuration of the Xanbus AGSTo change operational settings on the AGS Menu Accessing the AGS MenuXanbus Automatic Generator Start AGS Menu Xanbus AGS Menu To configureAGS Configuration Menu Contents Value Description Configuration MenuQT En QT Begin Gen Type QT EndDescription Cfg Trigger Start DCV 30 sec Values DefaultStart DCV 15 min Start DCV 24 hr Start DCV 2 hrStop Absorb Stop FloatStop Temp2 Temp1Start Load Value DefaultLoad Stop Load Starter Cool Down Cfg GenGen Spin Down Gen Cool DownExercise Per Max Run TimeExercise Time Exercise DurGen Run Hold Time Relay3Preheat Time Crank DelayCrank Time Crank Retry TimeGen Start Tries GenMode Restore DefaultsAutomatic Mode Manual Off Mode Manual On ModeView Event Log View Fault LogMode View Device InfoItems User SettingsOperation of the Xanbus AGS Accessing the AGS Home ScreenTo start the generator manually Starting and Stopping the GeneratorTo enable Quiet Time Using Quiet TimeModes of Operation Putting the AGS in Standby ModeTo return the AGS to Operating Mode Returning the AGS to Operating ModeTo view a message from a fault list or warning list TroubleshootingTroubleshooting AGS Warning Messages AGS Fault Messages Fault Reference TableRegulatory Approvals SpecificationsElectrical Specifications Environmental SpecificationsDimensions Weight Mounting Connectors Physical SpecificationsWarranty Warranty and Return InformationDisclaimer Warranty and Return InformationReturn Procedure Return Material Authorization PolicyInformation About Your System Generator Starting Types Recommended FeaturesAppendix a Generator Auto Start Requirements and Types Three-Wire Onan Two WireThree-Wire Automotive RunMode Appendix B Relay TimingMomentaryRun Mode Timing Diagram MomentaryRun ModeGlowStop Mode Timing Diagram GlowStop ModeStartStop Mode Timing Diagram StartStop ModePulseStop Mode Timing Diagram PulseStop ModePulseStop Mode Relay 1 Behavior Page Page Xantrex Technology USA Inc