Configuration of the Xanbus AGS
QT End
Full name Quiet Time End
Purpose "QT End" is a changeable setting that defines the end of quiet time.
This setting also requires a setting for "QT Begin".
Dependencies "QT End" functions only if the AGS is in Automatic mode. This setting requires "QT En" be set to [Enabled] and also requires a setting for "QT Begin".
Ensure the clock on the Xanbus System Control Panel (SCP) is set to the correct local time.
Gen Type
Full name Generator Type
Purpose "Gen Type" selects the starting requirements of the generator. The starting requirements determine how the AGS must be wired to the generator’s starting system. For more information, see “Connecting the Generator” on page 14 or Appendix B.
IMPORTANT: "Gen Type" can only be changed after the system is put into Standby. See “Putting the AGS in Standby Mode” on page 67.
Table 4 Generator Type Descriptions
Value | Description |
|
|
12:00AM to | At the time set for "QT End" the AGS will be |
11:59PM | able to automatically start the generator again. If |
clock) | a start trigger has occurred during quiet time and |
00:00 to 23:59 | is still active, the generator will start immediately |
after quiet time ends. | |
|
|
| Description |
|
|
|
|
Option | Mode | For Technical Details, see.a |
|
|
|
Type 1 | GlowStop | page 15 |
|
|
|
Type 2 | GlowStop with no preheat | page 16 |
|
|
|
Type 3 | GlowStop with shutdown bypass | page 17 |
|
|
|
Type 4 | StartStop with Relay 3 prime | page 18 |
|
|
|
Type 5 | StartStop with Relay 3 preheat | page 19 |
|
|
|
Type 6 | GlowStop with normally closed RunStop contact | page 20 |
|
|
|
Type 7 | Run with preheat | page 21 |
|
|
|
Type 8 | Run with no preheat | page 22 |
|
|
|
Type 9 | StartStop with Relay 3 preheat and shutdown | page 23 |
| bypass |
|
Type 10 | StartStop | page 24 |
|
|
|
Type 11 | MomentaryRun | page 25 |
|
|
|
42 | Xanbus Automatic Generator Start (AGS) Owner’s Guide |