Xanbus Automatic Generator Start Installation
EQUIPMENT DAMAGE
Tapping
Failure to follow these instructions can damage the unit and/or damage other equipment.
Table 3 Wiring for Connecting an External Manual ON/OFF Switch
Wire |
| Wiring Harness |
Number | Function | Wire Color |
|
|
|
7 | External manual on input | White/Green |
8 | External manual off input | White/Red |
9 | External On/Off LED Indicator | White/Blue |
| output |
|
10 | Constant 12/24 V B+ for External | Red |
| On/Off/LED Indicator |
|
11 | External On/Off/LED Indicator | Black |
| return |
|
|
|
|
Multiple generator control panels or simple contact closures can be wired to the external manual ON/OFF inputs. The AGS detects if any of the contacts close and will change its operating mode to External Manual On or External Manual Off (for more information, see “GenMode” on page 60). The AGS turns the generator on or off according to these inputs and the resulting operating mode change.
The External Manual On and External Manual Off states are not affected by maximum generator run time (see “Max Run Time” on page 55).
Connecting an External ON/OFF LED
Wires 9 (White/Blue) and 11 (Black) on the wiring harness can be connected to an LED or other light to accompany a remote external ON/ OFF switch. This light turns on when the generator run signal is active to visually indicate that the generator is running.
IMPORTANT: With some generators, the generator run signal becomes active during the preheat stage, before the generator is actually running. In this case, the external ON/OFF LED (and the Generator On light on the AGS) will turn on during the preheat stage and remain on when the generator is running.
For some generators, these lights will also remain on for a period of time after the generator has stopped.