Xanbus Automatic Generator Start Installation
Type 3
Type 3 is a
AGS Harness W ires | Generator W ires |
Relay Function | Preset Configuration Setting |
|
|
Preheat to crank delay | 0 s |
|
|
Crank time | 15 s |
|
|
Crank retry time | 30 s |
|
|
Gen Cool Down | 30 s |
|
|
Gen Spin Down | 3 s |
|
|
Shutdown bypass time | 10 s |
12
13
14
Relay 1
16
17
Relay 2
18
5A fuse
5A fuse
GENERATOR RUN SIGNAL GENERATOR RUN SIGNAL RETURN
PREHEAT
STOP
BYPASS SHUTDOWN START
Start tries | 3 |
For additional information, see “Circuit Limitations” on page 11.
Figure 9 Type 3 Connection Diagram
Relay Function | Preset Configuration Setting |
|
|
Relay 1 mode | GlowStop/Shutdown bypass |
Relay 3 mode | Preheat/Shutdown bypass |
|
|
Gen Run signal hold time | 0.5 s |
|
|
Preheat time | 20 s |
|
|
17 |