Xanbus Automatic Generator Start Installation
Type 9
Type 9 is a StartStop mode configuration with shutdown bypass functionality on relay 3.
Relay Function | Preset Configuration Setting |
|
|
Crank time | 15 s |
|
|
Crank retry time | 30 s |
AGS Harness W ires
Generator W ires |
Relay 1
Relay 2
Relay 3
12
13
14
16
17
18
19
20
|
|
|
| GENERATOR RUN SIGNAL |
|
|
|
| |
|
|
|
| GENERATOR RUN SIGNAL RETURN |
|
|
| 5A fuse | |
|
|
| STOP | |
|
|
| ||
|
| |||
|
|
| ||
|
|
| 5A fuse | START |
|
|
| ||
|
|
| ||
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
5A fuse FUEL PRIME (PREHEAT)
12V GENERATOR BATTERY+
Gen Cool Down | 30 s |
|
|
Gen Spin Down | 3 s |
|
|
Shutdown bypass time | 5 s |
|
|
Start tries | 3 |
For additional information, see “Circuit Limitations” on page 11.
Figure 17 Type 9 Connection Diagram
Relay Function | Preset Configuration Setting |
|
|
Relay 1 mode | StartStop |
Relay 3 mode | Shutdown Bypass |
|
|
Gen Run signal hold time | 0.5 s |
|
|
Preheat time | 0 s |
|
|
Preheat to crank delay | 0 s |
|
|
23 |