Xanbus Automatic Generator Start Installation
Type 10
Type 10 is a StartStop mode configuration with no preheat signal or shutdown bypass functionality.
AGS Harness W ires | Generator W ires |
Relay Function | Preset Configuration Setting |
|
|
Gen Cool Down | 30 s |
|
|
Gen Spin Down | 3 s |
|
|
Shutdown bypass time | 0 s |
Relay 1
Relay 2
12
13
14
16
17
18
GENERATOR RUN SIGNAL GENERATOR RUN SIGNAL RETURN
5A fuse | STOP |
5A fuse | START |
Start tries | 3 |
For additional information, see “Circuit Limitations” on page 11.
Figure 18 Type 10 Connection Diagram
Relay Function | Preset Configuration Setting |
|
|
Relay 1 mode | StartStop |
Relay 3 mode | No function |
Gen Run signal hold time | 0.5 s |
Preheat time | 0 s |
Preheat to crank delay | 0 s |
Crank time | 15 s |
Crank retry time | 30 s |
|
|
24 | Xanbus Automatic Generator Start (AGS) Owner’s Guide |