Troubleshooting
Warning Reference Table
Table 6 | AGS Warning Messages |
|
| |
|
|
|
|
|
Warning | Message |
| Cause | Action |
Number |
|
|
|
|
|
|
|
|
|
W200 | Generator | No | Generator was stopped | Acknowledge the |
| was stopped |
| by an external Manual | warning. To resume |
| manually. |
| Off switch. | automatic starts and |
|
|
|
| stops, change the AGS |
|
|
|
| mode to [Automatic]. |
|
|
|
|
|
W201 | Generator | No | Generator was started | Acknowledge the |
| was started |
| by an external Manual | warning. To resume |
| manually. |
| On switch | automatic starts and |
|
|
|
| stops, change the AGS |
|
|
|
| mode to [Automatic]. |
|
|
|
|
|
W202 | Unable to | Yes | The AGS tried, but | No action required. The |
| start |
| could not start the | AGS will try to start the |
| generator. |
| generator. | generator again until it |
| AGS will try |
|
| reaches the maximum |
| again. |
|
| number of start tries. |
|
|
|
|
|
W203 | Manual Off: | No | The generator has run | Acknowledge the |
| Max |
| for its maximum | warning. Return the |
| generator run |
| allowable time. The | AGS to the desired |
| time reached. |
| AGS has stopped the | GenMode [Automatic |
| Reset |
| generator and changed | or ManualOn]. Ensure |
| GenMode. |
| the GenMode to | generator has fuel and |
|
|
| [ManualOff]. | is supplying the |
|
|
|
| required power for |
|
|
|
| battery charging and |
|
|
|
| loads. |
|
|
|
|
|
Table 6 | AGS Warning Messages (Continued) |
| ||
|
|
|
|
|
Warning | Message | Cause | Action | |
Number |
|
|
|
|
|
|
|
|
|
W205 | Generator | Yes | The generator was | Check your generator. |
| started by its |
| started, but not by the | Stop it using the switch |
| switch. Use |
| AGS. | or control panel on the |
| its switch to |
|
| generator. |
| stop. |
|
|
|
|
|
|
|
|
W206 | Mismatched | No | You have set a start | Acknowledge warning |
| triggers. |
| trigger, but not a | and set a stop trigger. |
| Enable stop |
| corresponding stop |
|
| trigger or |
| trigger. |
|
| disable start |
|
|
|
| trigger. |
|
|
|
|
|
|
|
|
W207 | Mismatched | No | You have set a stop | Acknowledge warning |
| triggers. |
| trigger, but not a | and set a start trigger. |
| Enable start |
| corresponding start |
|
| trigger or |
| trigger. |
|
| disable stop |
|
|
|
| trigger. |
|
|
|
|
|
|
|
|
W208 | Automatic | No | You are attempting to | Acknowledge warning |
| start and stop |
| enter Automatic Mode | and set start and stop |
| triggers not |
| without setting triggers. | triggers. |
| enabled. |
|
|
|
| Configure |
|
|
|
| triggers. |
|
|
|
|
|
|
|
|
70 | Xanbus Automatic Generator Start (AGS) Owner’s Guide |