GAS INSTRUCTIONS

11

TEST CONNECTIONS

All connections and joints must be thoroughly tested for leaks in accordance with local codes and all listed procedures in the latest edition of the National Fuel Gas Code ANSI Z223.1/NFPA 54, Natural Gas and Propane Installation Code, CSA B149.1, or Propane Storage and Handling Code, B149.2, or the Standard for Recreational Vehicles, ANSI A 119.2/NFPA 1192, and CSA Z240 RV Series, Recreational Vehicle Code, as applicable.

DANGER

Do not use an open flame to check for gas leaks. Be sure there are no sparks or open flames in the area while you check for gas leaks. This will result in a fire or explosion which can cause serious bodily injury or death, and damage to property.

TYPICAL 20 LP PROPANE GAS SUPPLY INSTALLATION

The remote tank enclosure kit provided with your Weber Built-In grill shall be used for installations using a 20 lb LP cylinder, mounted in an “island” structure.

The remote tank enclosure shall house the included hose and regulator assembly and gas connections, the tank bracket and the fuel scale for connecting a remote mounted LP cylinder to the Summit® Built-In gas grill. The hose and regulator is listed as a required part of the CSA listed Summit® Built-In gas grill.

A properly installed tank enclosure meets the requirements for venting, tank retention and separation of the LP cylinder from a heat source as outlined in the ANSI Standard for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6 for LP enclosures.

You need to hire a licensed contractor or licensed plumber and they need to follow the requirements described in the ANSI Standard for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6 for LP enclosures.

The requirements described in the Standard for Outdoor Cooking Gas Appliances, Z21.58/CSA 1.6. are as follows;

A remote enclosure for an LP gas cylinder shall be ventilated by openings at both the upper and lower levels of the cylinder. This shall be accomplished by one of the following:

A)One side of the remote LP cylinder enclosure shall be completely open; or

B)If the remote LP cylinder enclosure is designed to have four sides, a top and a bottom, ventilation is required for the remote LP cylinder enclosure;

1)There should be at least two ventilation openings, (a hole or group of holes, for the purpose of ventilation) in the sidewalls of the island structure. The openings should be located within 5 inches (127mm) of the top of the enclosure. The ventilation openings should be equally sized and spaced at a minimum of 90 degrees, and be unobstructed. The openings shall have a total free open area of not less than 20 square inches. (This relates to 1 square inch of ventilation area, per pound of stored fuel capacity).

2)Ventilation openings (a hole or group of holes, for the purpose of ventilation) should be provided at floor level. The ventilation openings should have a total free area of not less than 10 square inches. (This relates to 1/2 square inch of ventilation area, per pound of stored fuel capacity). There should be at least two ventilation openings if the ventilation openings at floor level are in the sidewall. The ventilation openings should be within 5 inches (127mm) of the floor. The ventilation openings should be of equal size and be spaced at a minimum of 90 degrees, and should be unobstructed.

3)The minimum size of the ventilation hole (s) should not be less than 1/4 inch.

4)The ventilation openings in the sidewalls should not allow venting into the empty or “hollow” area of the “island”. If a gas leak should occur or the LP cylinder should vent in the LP cylinder enclosure, the gas should not be allowed to vent or migrate into the empty or “hollow” area of the “island”. Ventilation openings in the sidewalls of the enclosure should only communicate with the outside of the “island” structure, so that the gas can dissipate outside of the “island” structure.

C)If the remote LP cylinder enclosure has four sides, a top and a bottom, and is intended for installation in a built-in “island” enclosure;

1)At least one ventilation opening (a hole or group of holes, for the purpose of ventilation) needs to be on one side of the enclosure that communicates with the outside of the “island” structure. If a gas leak should occur or the LP cylinder should vent in the LP cylinder enclosure, the gas should not be allowed to vent or migrate into the empty or “hollow” area of the “island”. Ventilation openings should only communicate with the outside of the “island” structure, so that the gas can dissipate outside of the “island” structure. The ventilation opening should be located within 5 inches (127mm) of the top of the enclosure, and should have a total free area of 20 square inches. (This relates to 1 square inch of ventilation area, per pound of stored fuel).

2)At least one ventilation opening (a hole or group of holes, for the purpose of ventilation) needs to be on one side of the enclosure that communicates with the outside of the “island” structure, at the bottom. If a gas leak should occur or the LP cylinder should vent in the LP cylinder enclosure, the gas should not be allowed to vent or migrate into the empty or “hollow” area of the “island”. Ventilation openings should only communicate with the outside of the “island” structure, so that the gas can dissipate outside of the “island” structure. The ventilation opening should be located within 5 inches (127mm) of the bottom of the enclosure, and should have a total free area of 10 square inches. (This relates to 1/4 square inch of ventilation area, per pound of stored fuel).

3)The minimum size of the ventilation hole (s) should not be less than 1/4 inch (6.35mm).

D)The remote LP cylinder enclosure should be constructed with non-combustible materials. The remote LP cylinder enclosure should isolate the LP cylinder from the burner compartment, so that it provides shielding from radiation, be a flame barrier and provide protection from foreign material such as hot drippings.

E)There should be a minimum of 2 inches (50.8mm) between the ground and the floor of the remote LP cylinder enclosure.

F)The LP cylinder valve should be readily accessible for hand operation. A door on the remote LP cylinder enclosure to gain access to the LP cylinder valve is acceptable, provided it is non-locking and can be opened without the use of tools.

WWW.WEBER.COM®

Image 11
Contents #56069 Liquid Propane GAS Units only Wash hands after handling this productGarantie WARRANTY, GARANTÍA, GarantieWarranty GarantíaExploded VIEW, Diagrama DE DESPIECE, Vision Eclatee Grate Side Burner Box Igniter Module Hardware LIST, Lista DE LOS HERRAJES, Liste DU MaterielOperating InstallationFor Installation in Canada Island Structure Configuration OptionsClearance from Combustible Surfaces or Structures InstallationBUILT-IN Structure Cutout Dimensions Locating Your BUILT-IN Side Burner ApplianceGeneral Construction Details BUILT-IN GAS Line LocationsMounting the Side Burner Installation GAS Line Piping INSTALLATION/GAS InstructionsTypical Bulk Propane GAS Supply Installation Test Connections Typical 20 LP Propane GAS Supply InstallationGAS Instructions Connect GAS Supply Connecting GAS SupplyLeak Check Preparation Connecting GAS SupplyConnecting the Liquid Propane Cylinder Important LP Cylinder InformationCheck for GAS Leaks GAS Leak TestingTo Connect the Hose to the Cylinder Check GAS Supply Connections Check Side Burner ComponentLiquid Propane LP Cylinders GAS InstructionsSafe Handling Tips for Liquid Propane GAS Cylinders CanadaTo Extinguish Operating InstructionsSide Burner Lighting Instructions Manually Lighting the Side Burner Operating InstructionsSide Burner Maintenance Side Burner TroubleshootingGeneral Maintenance Problem Check CureBurner Flame Pattern General MaintenanceCleaning Herrajes PG #42376Únicamente Unidades DE GAS Propano Licuado Peligros Y AdvertenciasPeligro AdvertenciasPara LA Instalación EN Canadá Opciones DE Configuración DE LAS Estructuras Tipo IslaInstalación OperaciónSeparación DE LAS Superficies O Estructuras Combustibles Dimensiones seccionales ToleranciasInstalación Ubicación DEL Quemador Lateral EmpotradoDetalles Generales DE Construcción Ubicaciones DE LAS Líneas DE GAS EmpotradasMontaje DEL Quemador Lateral Instalación Especificaciones Generales Para LA Tubería INSTALACIÓN/INSTRUCCIONES Para EL GASInstalación Típica DE Suministro DE GAS Propano a Granel Tubería DE LA Línea DE GASPruebe LAS Conexiones Instrucciones Para EL GASConectar EL Suministro DE GAS Conexión DEL Suministro DE GASLlene EL Cilindro DE Propano Licuado Conexión DEL Suministro DE GASPreparativos Para LA Búsqueda DE Fugas Conexión DEL Cilindro DE Propano LicuadoCompruebe QUE no Haya Fugas DE GAS Pruebas Para Detectar Fugas DE GASPara Conectar LA Manguera AL Cilindro Revise LAS Conexiones DE Suministro DE GAS Pruebas Para Detectar Fugas DE GASRevise EL Quemador Lateral EN Canadá Requisitos DE LOS Cilindros DE Propano Licuado Instrucciones Para EL GASCilindros DE Propano Licuado Requisitos DE LOS Cilindros DE Propano LicuadoPara Apagar Instrucciones DE OperaciónInstrucciones Para Encender EL Quemador Lateral AdvertenciaEncendido Manual DEL Quemador Lateral Peligro Instrucciones DE OperaciónEncendedor Resolución DE Problemas CON EL Quemador LateralProblema Revisar Remedio Mantenimiento GeneralLimpieza Patrón DE LA Llama DEL QuemadorMateriel PG 42376Appareils a GAZ Propane Uniquement Mises EN GardeUtilisation Pour L’INSTALLATION AU CanadaOptions DE Configuration Pour LA Structure EN Ilot Brûleur latéral Dimensions Pour LE Decoupage DE LA Structure IntegreeDimensions pour le découpage Tolérances Localisation DE Votre Bruleur Lateral IntegreGeneralites SUR LA Construction Emplacements DE LA Conduite DE GAZ IntegreeMontage DU Bruleur Lateral Installation Generalites Relatives AUX Canalisations Instructions Pour L’INSTALLATION/GAZInstallation D’ARRIVEE DE GAZ Propane EN Vrac Typique Canalisations DE GAZTest DES Raccords Installation DE L’ALIMENTATION EN GAZ PropaneInstructions Relatives AU GAZ Raccordement DE L’ARRIVEE DE GAZ Raccordement DE L’ARRIVEE DE GAZConnexion DE LA Bouteille DE Propane Liquide Raccordement DE L’ARRIVEE DE GAZInformations Importantes Relatives a LA Bouteille DE PL Preparation DE LA Detection DES FuitesDetection DES Fuites DE GAZ Detection DES Fuites DE GAZPour Connecter LE Tuyau À LA Bouteille Verifiez LES Raccords DE L’ARRIVEE DE GAZ Verifiez LES Composants DU Bruleur LateralAU Canada Instructions Relatives AUX GAZBouteilles DE GAZ Propane Liquide PL Exigences Relatives À LA Bouteille DE Propane LiquidePour Eteindre Mode D’EMPLOIInstructions Pour L’ALLUMAGE DU Bruleur Lateral Mise EN GardeAllumage Manuel DU Bruleur Lateral Mode D’EMPLOIDepannage DU Bruleur Lateral Maintenance GeneraleProbleme Verification Solution Maintenance DU Bruleur LateralNettoyage Maintenance GeneraleAspect DE LA Flamme DU Bruleur Page WEBER-STEPHEN Products CO