CB1200-I Pellet Insert
Troubleshooting (Cont’d)
Symptom | Possible Cause | Corrective Action |
Slow or smoky | Dirty exhaust and/or venting system. | Check for ash build up in appliance, |
(Cont’d) |
| including behind rear panels, firebox, heat |
|
| exchanger, exhaust blower and venting. |
Feed system fails to | Out of fuel. | Check hopper, fill with fuel. |
start. | #2 snap disc may be defective. | Replace snap disc. Firebox door must be |
| ||
|
| closed securely. |
| Vacuum switch not closing. No vacuum. | Check exhaust blower is plugged in and |
|
| operating. |
|
| Check vacuum switch is plugged in. |
|
| Check vacuum hose is in good condition, |
|
| clear and connected at both ends. |
|
| Check thermocouple is in good condition |
|
| and plugged in properly. |
|
| Make sure venting system is clean. |
|
| NOTE: High winds blowing into the vent- |
|
| ing system can pressurize the firebox |
|
| causing loss of vacuum. |
| Feed system jammed or blocked. | Empty hopper of fuel. Use a wet/dry |
|
| vacuum cleaner to remove remaining fuel, |
|
| from hopper, including feed tube. |
|
| Check feed chute for obstructions. |
|
| Loosen 2 screws and jiggle feed assembly. |
| Feed spring not turning with feed motor. | Check that set screw is tight on feed |
|
| spring shaft at end of feed motor. |
| Feed motor defective or not plugged in. | Check connections on feed motor, replace |
|
| if defective. |
No call light. Appliance | Thermostat not set to a high enough tempera- | Adjust thermostat above room tempera- |
does not begin start | ture. | ture. |
sequence. | Snap Disc #3 tripped. | Reset snap disc. |
| ||
| No power. | Connect to power. |
| Fuse blown. | Replace fuse. |
| Connections at thermostat and/or appliance not | Check connections at thermostat and |
| making proper contact. | appliance. |
| Defective thermostat or thermostat wiring. | Replace thermostat or wiring. |
|
| NOTE: To test thermostat and wiring, use |
|
| a jumper wire at the thermostat block on |
|
| the appliance to |
|
| wiring. |
| Control box defective. | Replace control box. |
|
| |
Appliance fails to shut | Call light on. | Turn thermostat off. |
off. |
| If call light does not go out, disconnect |
|
| thermostat wires from appliance. If call |
|
| light does go out, thermostat or wires are |
|
| defective. |
|
|
|
February 3, 2010 | Page 31 |