Installation
TCP Model
Assembly
Instructions
If your nameplate model number begins with TCP, use the assembly instructions below.
Joining Sections Edge-to- Edge
Units must be installed level for proper drainage of condensate from the drain pan. In addition, each section in a
Note: Leveling each section, beginning with the first, is critical. Failure to level and align the sections immediately creates greater
two sections should be within 12 inches to reduce the amount of dragging required.
6Remove lifting lugs on mating section as required.
7Insert threaded rods through each hole of each mating connecting plate (see Figure 4). Bring each connecting surface together uniformly until gasketing is contacted.
Note: Use field provided threaded rods inserted in all holes of each connecting plate to prevent damage and distortion of the sections as they are joined. Tighten all rods in sequence. Do not try to join sections by tightening only some of the rods.
Note: Failure to compress the gasketing may result in air leakage.
8Secure the unit sections at the base using the field provided bolts, nuts and washers at the connecting plates.
9Once the sections are pulled together, install the assembly hardware as applicable for the walls, roof, and the base as demonstrated in the following assembly sections.
misalignment or even structural damage afterward.
1Remove all crating and wrapping from the surfaces to be joined.
2Place one section of the air handler into the desired position. Verify each section is level and properly supported prior to proceeding with assembly. Each unit must be level
3When the unit is positioned and squareness is assured within 1/8- inch, remove all lifting lugs located along the split plane.
4Install
5Move the next mating section into alignment with the positioned section. Alignment of sections must be completed before gasket surfaces meet. The
Figure 4. Insert threaded rods through each hole of mating connecting plate.
12 |
|