Troubleshooting

Table 5. Air handler troubleshooting recommendations

Symptom

Probable Cause

Recommended Action

Short belt life

Worn sheaves

Replace sheaves.

 

Misaligned belt

Realign drive with MVP sheave set at mean pitch diameter.

 

Grease or oil on belts

Check for leaky bearings. Clean belts and sheaves.

 

Belt slipping

Improper belt tension. Adjust tension.

 

Belts rubbing

Remove obstruction or realign drive for clearance.

 

 

 

Bearing noise

Poor alignment

Loosen bearing set screws and realign (see the “Bearing Set Screw

 

 

Alignment” section on page 50).

 

Failed bearing

Replace bearing.

 

Inadequate lubrication

Replace bearing.

 

 

 

Low water coil

Incorrect airflow

Check fan operating condition.

capacity

Incorrect water flow

Inspect the water pumps and valves for proper operation and check

 

 

the lines for obstructions.

 

Incorrect water temperature

Adjust the chiller or boiler to provide the proper water

 

 

temperature.

 

Coil is piped incorrectly

Verify coil piping (see the “Coil Piping and Connections” section on

 

 

page 28.

 

Dirty fin surface

Clean the fin surface (see the “Coils” section on page 52).

 

Incorrect glycol mixture

Verify glycol mixture and adjust if necessary.

 

 

 

Low refrigerant coil

Incorrect airflow

Check fan operating condition.

capacity

Expansion valve is not operating properly or is

Check sensing bulb temperature.

 

sized incorrectly

Verify valve operation.

 

 

Verify proper valve size.

 

Incorrect refrigerant charge

Verify refrigerant charge and adjust if necessary.

 

Condensing unit failure

Verify condensing unit operation.

 

Coil is piped incorrectly

Verify coil piping (see the “Coil Piping and Connections” section on

 

 

page 28).

 

Clogged refrigerant line filter

Change filter core.

 

Failure of suction/liquid line components

Verify component operation

 

Dirty fin surface

Clean the fin surface (see the “Coils” section on page 52).

 

 

Note: Do not use steam to clean refrigerant coils.

 

Fin frosting

Verify defrost cycle operation.

 

 

Verify frostat operation.

 

 

Verify refrigerant charge.

 

 

 

Low steam coil

Incorrect airflow

Check fan operating condition.

capacity

Coil is piped incorrectly

Verify coil piping (see the “Coil Piping and Connections” section on

 

 

page 28).

 

Incorrect steam pressure

Verify steam pressure and adjust if necessary.

 

Excessive steam superheat

Check steam superheat.

 

 

Steam superheat should not exceed 50ºF.

 

Failure of steam line/condensate return

Verify component operation

 

components

 

 

Boiler failure

Verify boiler operation

 

Dirty fin surface

Clean the fin surface (see the “Coils” section on page 52).

 

 

 

Drain pan is

Plugged Drain Line

Clean drain line

overflowing

Unit not level

Level unit

 

Improper trap design

Design trap per unit installation instructions

 

 

 

Standing water in

Improper trap design

Design trap per unit installation instructions

drain pan

Unit not level

Level unit

 

Plugged Drain Line

Clean drain line

 

 

 

Wet interior

Coil face velocity too high

Reduce fan speed

insulation

Improper trap design

Design trap per unit installation instructions

 

Drain pan leaks/overflows

Repair leaks

 

Condensation on surfaces

Insulate surfaces

 

 

 

Excess dirt in unit

Missing filters

Replace filters

 

Filter bypass

Reduce filter bypass by ensuring all blockoffs are in place.

 

 

 

Microbial growth

Standing water in drain pan

See “Standing water in drain pan”

(mold) inside air handler

CAH-SVX01A-EN

57

Image 57
Contents July Custom Climate Changer Air HandlersCAH-SVX01A-EN Protecting Environment Unit DescriptionContents Operating Environment Wiring Sizes ConnectionsControls Factory-Mounted ControlsUltraviolet UV Germicidal Irradiation Lights optional Resolving Shipping Damage Receiving ChecklistJob Site Storage Recommendations Use Canvas OnlyPreparing the Unit Site Pre-Installation Requirements General StorageLong-Term Storage Outdoor Storage ConsiderationsTypical Curb Installation Checklist Roof Curb InstallationGeneral Lifting Considerations Lifting and RiggingAssembly Hardware Unit AssemblyJoining Sections Edge-to- Edge TCP Model Assembly InstructionsTCP base assembly TCP Base Section Assembly TypicalTCP Outdoor Roof Section Assembly Typical Installation TCP Wall Section Assembly TypicalInstallation TCP Indoor Roof Section Assembly Typical Indoor Roof Assembly CompleteBase to Wall Assembly Complete Joining sections Edge to Edge TCC Model Assembly InstructionsApply butyl tape to shipping splits Add caulk along the seam Join internal shipping split frame Installation TCC indoor roof sections assembly typical TCC wall sections assembly typicalJoin outdoor roof panels at the seams Installation TCC outdoor roof sections assembly typicalTrim roof joint strip Isolator Adjustment Component Installation RequirementsDuct Connections FansTraq Dampers Control DampersMagnahelic Air Filter Gage Front Load Filters Installation Air FiltersBag or Cartridge Filters Outdoor Unit Weather HoodsCoil Piping Connections Use a Backup WrenchGeneral Recommendations Prevent Coil DamageWater Damage Installation Drain Pan TrappingCoil Damage Installation Steam Coil PipingInstallation Typical piping for type 5W one-row water coil Water Coil PipingLiquid Lines Installation Refrigerant Coil PipingType F refrigerant coil with packed elbow Valve DamageSingle-circuit evaporator coil with one distributor Examples of Field-Installed Evaporator PipingSingle-circuit evaporator coil with two distributors Single-circuit evaporator coil with four distributors Dual-circuit evaporator coil with two distributors Dual-circuit evaporator coil with four distributors Dual-circuit evaporator coil with eight distributors Hazardous Voltage with WiringUse Copper Conductors Only CapacitorsExternal Insulating Requirements Junction box mounting and wiring detailsFan-Related Checks Pre-Startup ChecklistCoil-Related Checks Proper Water Treatment Motor-Related ChecksUnit Operation General ChecksCalculate Motor Voltage Imbalance Tension Belts Correctly Startup Tension the Fan BeltStartup Determine Fan Speed Sheave AlignmentMultibelt Check Routine Maintenance Throwaway Filters Air FiltersPermanent Filters Front Load FiltersDrain Pans Inspecting and Cleaning FansFans Bearing Set Screw AlignmentFan Motor Inspection Fan Bearing LubricationSteam and Water Coils CoilsType K Cooling Coils Refrigerant CoilsMoisture Purge Cycle Internal Insulation Ultraviolet UV Germicidal Irradiation Lights Replacement of ultraviolet bulbsTroubleshooting Alignment section on CAH-SVX01A-EN CAH-SVX01A-EN Trane