Trane CAH-SVX01A-EN manual Unit Operation, General Checks, Calculate Motor Voltage Imbalance

Page 44

General Checks

Ensure the unit has been installed level.

Ensure supply-air and return-air ducts have been connected.

Ensure damper operator motors and connecting linkage have been installed.

Verify damper operation and linkage alignment.

Check that air filters are in place and positioned properly.

Remove any debris from the unit interior.

Close and secure all unit access doors.

Note: UL-listed units require a removable latch on access doors. The door clip shipped with the unit meets this requirement.

Inspect electrical connections to the unit and unit controllers.

Connections should be clean and secure.

Compare the actual wiring with the unit diagrams.

Reference the appropriate controller manual for more details about starting units with factory-mounted controls.

Leave this manual with the unit.

44

Startup

Unit Operation

Before complete startup, bump-start the unit and confirm the fan wheel rotates properly, as indicated by the rotation arrow located on the fan housing.

After initial startup:

Calculate the motor voltage imbalance, notifying the power company to correct unacceptable imbalances.

Periodically check the fan belt tension.

Calculate Motor

Voltage Imbalance

After startup, measure the motor voltage and amperage on all phases to ensure proper operation. The readings should fall within the range given on the motor nameplate. The maximum allowable voltage imbalance is 2 percent.

Voltage imbalance is defined as 100 times the sum of the deviation of the three voltages from the average, divided by twice the average voltage. For example, if the three measured voltages are 221, 230 and 227, the average voltage would be 226 volts. The percent of voltage imbalance is then calculated:

Voltage imbalance =

100A

2--------------------------------------------------AvgVoltage

where:

A = (226-221) + (230-226) + (227-226)

Voltage imbalance = 2.2% (not acceptable)

In the example, 2.2 percent imbalance is not acceptable and the power company should be notified to correct it.

￿WARNING Live Electrical Components!

During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.

CAH-SVX01A-EN

Image 44
Contents Custom Climate Changer Air Handlers JulyCAH-SVX01A-EN Unit Description Protecting EnvironmentContents Wiring Sizes Connections Operating EnvironmentControls Factory-Mounted ControlsUltraviolet UV Germicidal Irradiation Lights optional Receiving Checklist Resolving Shipping DamageJob Site Storage Recommendations Use Canvas OnlyPre-Installation Requirements General Storage Preparing the Unit SiteLong-Term Storage Outdoor Storage ConsiderationsRoof Curb Installation Typical Curb Installation ChecklistLifting and Rigging General Lifting ConsiderationsUnit Assembly Assembly HardwareTCP Model Assembly Instructions Joining Sections Edge-to- EdgeTCP Base Section Assembly Typical TCP base assemblyInstallation TCP Wall Section Assembly Typical TCP Outdoor Roof Section Assembly TypicalIndoor Roof Assembly Complete Installation TCP Indoor Roof Section Assembly TypicalBase to Wall Assembly Complete TCC Model Assembly Instructions Joining sections Edge to EdgeApply butyl tape to shipping splits Add caulk along the seam Join internal shipping split frame TCC wall sections assembly typical Installation TCC indoor roof sections assembly typicalInstallation TCC outdoor roof sections assembly typical Join outdoor roof panels at the seamsTrim roof joint strip Component Installation Requirements Isolator AdjustmentDuct Connections FansMagnahelic Air Filter Gage Traq DampersControl Dampers Installation Air Filters Front Load FiltersOutdoor Unit Weather Hoods Bag or Cartridge FiltersUse a Backup Wrench Coil Piping ConnectionsGeneral Recommendations Prevent Coil DamageInstallation Drain Pan Trapping Water DamageInstallation Steam Coil Piping Coil DamageInstallation Water Coil Piping Typical piping for type 5W one-row water coilInstallation Refrigerant Coil Piping Liquid LinesValve Damage Type F refrigerant coil with packed elbowExamples of Field-Installed Evaporator Piping Single-circuit evaporator coil with one distributorSingle-circuit evaporator coil with two distributors Single-circuit evaporator coil with four distributors Dual-circuit evaporator coil with two distributors Dual-circuit evaporator coil with four distributors Dual-circuit evaporator coil with eight distributors Wiring Hazardous Voltage withUse Copper Conductors Only CapacitorsJunction box mounting and wiring details External Insulating RequirementsPre-Startup Checklist Fan-Related ChecksCoil-Related Checks Proper Water Treatment Motor-Related ChecksCalculate Motor Voltage Imbalance Unit OperationGeneral Checks Startup Tension the Fan Belt Tension Belts CorrectlyStartup Multibelt Check Determine Fan SpeedSheave Alignment Routine Maintenance Air Filters Throwaway FiltersPermanent Filters Front Load FiltersInspecting and Cleaning Fans Drain PansFans Bearing Set Screw AlignmentFan Bearing Lubrication Fan Motor InspectionCoils Steam and Water CoilsType K Cooling Coils Refrigerant CoilsMoisture Purge Cycle Internal Insulation Replacement of ultraviolet bulbs Ultraviolet UV Germicidal Irradiation LightsTroubleshooting Alignment section on CAH-SVX01A-EN CAH-SVX01A-EN Trane