Trane CAH-SVX01A-EN manual Water Coil Piping, Typical piping for type 5W one-row water coil

Page 32

Installation

unless the condensate is drained by gravity into a receiver, vented to atmosphere, and returned to the condensate pump.

6Pitch all supply and return steam piping down 1 inch for every 10 feet in the direction of the steam or condensate flow.

Note: Do not drain the steam mains or take-offs through the coils. Drain the mains ahead of the coils through a steam trap to the return line.

7Ensure overhead returns have

1 psig of pressure at the steam trap discharge for every 2 feet of elevation for continuous condensate removal.

Water Coil Piping

Figure 30 through Figure 32 illustrate typical water coil piping configurations.

Type WA, 5A, 5W, D, K, W, UW, TT, P,2, P4, and P8 water coils are self- venting only if the water velocity exceeds 1.5 feet per second (fps) in the coil tubes. Type UU, WD, and 5D water coils are self-venting only if the water velocity exceeds 2.5 fps in the coil tubes. See the unit submittals for coil water velocity. If the water velocity is below these minimums, vent the coil by one of the following methods:

Install an air vent in the top pipe plug tapping of the return header.

When the return line rises above the top of the coil, vent from the top of the return header horizontally to the return piping.

Note: T, ST, and TT coils are designed with larger than normal end tube sheet holes to allow for maximum expansion. Air leakage around tubes should be expected and handled by capping over coil ends or by sealing around tubes with a pliable sealant such as silicone.

Figure 30. Typical piping for type 5W one-row water coil

Figure 31. Typical piping for type 5A, 5W two-row, K, W 3- to 12-row, WD, D, and DD water coils

Figure 32. Typical piping for type W or WA 1-row water coil

32

CAH-SVX01A-EN

Image 32
Contents Custom Climate Changer Air Handlers JulyCAH-SVX01A-EN Unit Description Protecting EnvironmentContents Wiring Sizes Connections Operating EnvironmentControls Factory-Mounted ControlsUltraviolet UV Germicidal Irradiation Lights optional Receiving Checklist Resolving Shipping DamageJob Site Storage Recommendations Use Canvas OnlyPre-Installation Requirements General Storage Preparing the Unit SiteLong-Term Storage Outdoor Storage ConsiderationsRoof Curb Installation Typical Curb Installation ChecklistLifting and Rigging General Lifting ConsiderationsUnit Assembly Assembly HardwareTCP Model Assembly Instructions Joining Sections Edge-to- EdgeTCP Base Section Assembly Typical TCP base assemblyInstallation TCP Wall Section Assembly Typical TCP Outdoor Roof Section Assembly TypicalIndoor Roof Assembly Complete Installation TCP Indoor Roof Section Assembly TypicalBase to Wall Assembly Complete TCC Model Assembly Instructions Joining sections Edge to EdgeApply butyl tape to shipping splits Add caulk along the seam Join internal shipping split frame TCC wall sections assembly typical Installation TCC indoor roof sections assembly typicalInstallation TCC outdoor roof sections assembly typical Join outdoor roof panels at the seamsTrim roof joint strip Component Installation Requirements Isolator AdjustmentDuct Connections FansMagnahelic Air Filter Gage Traq DampersControl Dampers Installation Air Filters Front Load FiltersOutdoor Unit Weather Hoods Bag or Cartridge FiltersUse a Backup Wrench Coil Piping ConnectionsGeneral Recommendations Prevent Coil DamageInstallation Drain Pan Trapping Water DamageInstallation Steam Coil Piping Coil DamageInstallation Water Coil Piping Typical piping for type 5W one-row water coilInstallation Refrigerant Coil Piping Liquid LinesValve Damage Type F refrigerant coil with packed elbowExamples of Field-Installed Evaporator Piping Single-circuit evaporator coil with one distributorSingle-circuit evaporator coil with two distributors Single-circuit evaporator coil with four distributors Dual-circuit evaporator coil with two distributors Dual-circuit evaporator coil with four distributors Dual-circuit evaporator coil with eight distributors Wiring Hazardous Voltage withUse Copper Conductors Only CapacitorsJunction box mounting and wiring details External Insulating RequirementsPre-Startup Checklist Fan-Related ChecksCoil-Related Checks Proper Water Treatment Motor-Related ChecksCalculate Motor Voltage Imbalance Unit OperationGeneral Checks Startup Tension the Fan Belt Tension Belts CorrectlyStartup Multibelt Check Determine Fan SpeedSheave Alignment Routine Maintenance Air Filters Throwaway FiltersPermanent Filters Front Load FiltersInspecting and Cleaning Fans Drain PansFans Bearing Set Screw AlignmentFan Bearing Lubrication Fan Motor InspectionCoils Steam and Water CoilsType K Cooling Coils Refrigerant CoilsMoisture Purge Cycle Internal Insulation Replacement of ultraviolet bulbs Ultraviolet UV Germicidal Irradiation LightsTroubleshooting Alignment section on CAH-SVX01A-EN CAH-SVX01A-EN Trane