Trane CAH-SVX01A-EN, Custom Climate Changer Air Handlers manual Startup

Page 46

Startup

Table 3. Typical sheave diameter and deflection force1

 

 

 

 

Belt Deflection Force (lbs)

 

 

Smallest Sheave

 

Super Gripbelts and

Gripnotch Belts and

Cross

Diameter Range

Speed (rpm)

Unnotched Gripbands

Notched Gripbands

Section

(in.)

Range

Used Belt

New Belt

Used Belt

New Belt

 

 

 

 

 

 

 

 

3.0–3.6

1,000–2,500

3.7

5.5

4.1

6.4

 

 

2,501–4,000

2.8

4.2

3.4

5.0

A, AX

3.8–4.8

1,000–2,500

4.5

6.8

5.0

7.4

 

2,501–4,000

3.8

5.7

4.3

6.4

 

 

 

5.0–7.0

1,000–2,500

5.4

8.0

5.7

9.4

 

 

2,501–4,000

4.7

7.0

5.1

7.6

 

 

 

 

 

 

 

 

3.4–4.2

860–2,500

n/a

n/a

4.9

7.2

 

 

2,501–4,000

n/a

n/a

4.2

6.2

B, BX

4.4–5.6

860–2,500

5.3

7.9

7.1

10.5

 

2,501–4,000

4.5

6.7

7.1

9.1

 

 

 

5.8–8.6

860–2,500

6.3

9.4

8.5

12.6

 

 

2,501–4,000

6.0

8.9

7.3

10.9

 

 

 

 

 

 

 

 

7.0–9.0

500–1,740

11.5

17.0

14.7

21.8

C, CX

 

1,741–3,000

9.4

13.8

11.9

17.5

9.5–16.0

500–1,740

14.1

21.0

15.9

23.5

 

 

 

1,741–3,000

12.5

18.5

14.6

21.6

 

12.0–16.0

200–850

24.9

37.0

n/a

n/a

D

 

851–1,500

21.2

31.3

n/a

n/a

18.0–20.0

200–850

30.4

45.2

n/a

n/a

 

 

 

851–1,500

25.6

38.0

n/a

n/a

 

 

 

 

 

 

 

 

2.2–2.4

1,000–2,500

n/a

n/a

3.3

4.9

 

 

2,501–4,000

n/a

n/a

2.9

4.3

3V, 3VX

2.65–3.65

1,000–2,500

3.6

5.1

4.2

6.2

 

2,501–4,000

3.0

4.4

3.8

5.6

 

 

 

4.12–6.90

1,000–2,500

4.9

7.3

5.3

7.9

 

 

2,501–4,000

4.4

6.6

4.9

7.3

 

 

 

 

 

 

 

 

4.4–6.7

500–1,749

n/a

n/a

10.2

15.2

 

 

1,750–3,000

n/a

n/a

8.8

13.2

 

 

3,001–4,000

n/a

n/a

5.6

8.5

5V, 5VX

7.1–10.9

500–1,749

12.7

18.9

14.8

22.1

 

 

1,750–3,000

11.2

16.7

13.7

20.1

 

11.8–16.0

500–1,749

15.5

23.4

17.1

25.5

 

 

1,750–3,000

14.6

21.8

16.8

25.0

 

 

 

 

 

 

 

 

12.5–17.0

200–850

33.0

49.3

n/a

n/a

8V

 

851–1,500

26.8

39.9

n/a

n/a

18.0–22.4

200–850

39.6

59.2

n/a

n/a

 

 

 

851–1,500

35.3

52.7

n/a

n/a

1. Source for table: Browning® catalog DC-98, page B-30.

46

CAH-SVX01A-EN

Image 46
Contents Custom Climate Changer Air Handlers JulyCAH-SVX01A-EN Unit Description Protecting EnvironmentContents Controls Wiring Sizes ConnectionsOperating Environment Factory-Mounted ControlsUltraviolet UV Germicidal Irradiation Lights optional Job Site Storage Recommendations Receiving ChecklistResolving Shipping Damage Use Canvas OnlyLong-Term Storage Pre-Installation Requirements General StoragePreparing the Unit Site Outdoor Storage ConsiderationsRoof Curb Installation Typical Curb Installation ChecklistLifting and Rigging General Lifting ConsiderationsUnit Assembly Assembly HardwareTCP Model Assembly Instructions Joining Sections Edge-to- EdgeTCP Base Section Assembly Typical TCP base assemblyInstallation TCP Wall Section Assembly Typical TCP Outdoor Roof Section Assembly TypicalIndoor Roof Assembly Complete Installation TCP Indoor Roof Section Assembly TypicalBase to Wall Assembly Complete TCC Model Assembly Instructions Joining sections Edge to EdgeApply butyl tape to shipping splits Add caulk along the seam Join internal shipping split frame TCC wall sections assembly typical Installation TCC indoor roof sections assembly typicalInstallation TCC outdoor roof sections assembly typical Join outdoor roof panels at the seamsTrim roof joint strip Duct Connections Component Installation RequirementsIsolator Adjustment FansControl Dampers Traq DampersMagnahelic Air Filter Gage Installation Air Filters Front Load FiltersOutdoor Unit Weather Hoods Bag or Cartridge FiltersGeneral Recommendations Use a Backup WrenchCoil Piping Connections Prevent Coil DamageInstallation Drain Pan Trapping Water DamageInstallation Steam Coil Piping Coil DamageInstallation Water Coil Piping Typical piping for type 5W one-row water coilInstallation Refrigerant Coil Piping Liquid LinesValve Damage Type F refrigerant coil with packed elbowExamples of Field-Installed Evaporator Piping Single-circuit evaporator coil with one distributorSingle-circuit evaporator coil with two distributors Single-circuit evaporator coil with four distributors Dual-circuit evaporator coil with two distributors Dual-circuit evaporator coil with four distributors Dual-circuit evaporator coil with eight distributors Use Copper Conductors Only WiringHazardous Voltage with CapacitorsJunction box mounting and wiring details External Insulating RequirementsCoil-Related Checks Proper Water Treatment Pre-Startup ChecklistFan-Related Checks Motor-Related ChecksGeneral Checks Unit OperationCalculate Motor Voltage Imbalance Startup Tension the Fan Belt Tension Belts CorrectlyStartup Sheave Alignment Determine Fan SpeedMultibelt Check Routine Maintenance Permanent Filters Air FiltersThrowaway Filters Front Load FiltersFans Inspecting and Cleaning FansDrain Pans Bearing Set Screw AlignmentFan Bearing Lubrication Fan Motor InspectionType K Cooling Coils CoilsSteam and Water Coils Refrigerant CoilsMoisture Purge Cycle Internal Insulation Replacement of ultraviolet bulbs Ultraviolet UV Germicidal Irradiation LightsTroubleshooting Alignment section on CAH-SVX01A-EN CAH-SVX01A-EN Trane