Trane CAH-SVX01A-EN manual Installation TCP Wall Section Assembly Typical

Page 14

Installation

TCP Wall Section Assembly (Typical)

1Apply the walls and join at the inside angles with number 14 sheet-metal screws on 12-inch centers along the length of the angles.

2Apply the 1/8-inch gasket evenly to the exterior of the walls across the two joined edges of the splits.

3Before installing the pre-cut joining strip over the gasket, pre- drill holes in the wall using the strip as a guide with a number 29 drill bit at 12-inch centers.

Figure 6. TCP outdoor roof assembly

4Apply the joining strip over the gasket and uniformly straddling the splits. Secure with number 10 sheet metal screws.

5Fit the pre-cut hub cap over the joining strip the vertical height of the wall flush with the roof and secure it to the wall with number 8 sheet metal screws. Fill the top and bottom openings with caulk as moisture seal. Pre drill holes with a number 29 bit.

TCP Outdoor Roof Section Assembly (Typical)

1Align the roof splits and join the interior section trim with number 14 sheet metal screws on 12 inch centers.

2Add a bead of caulk along the length of the roof seams. Install the pre-cut J-cap over the seam and secure with number 14 sheet metal screws on 12-inch centers.

Note: Use a polyurethane or equivalent caulk. It may be necessary to clamp the joint together or predrill to prevent separation when drilling with screws.

3Apply caulk to the end cap interior surface. Secure the end cap on the J-cap with one number 10 screw.

INSTALLING J-CAP

SPLIT

4" X 1/4" GASKET

SPLIT

SECTION TRIM ACTS AS

AS JOINING ANGLE

SECURE w/#14 S.M. @ 12" CENTERS.

APPLY CAULKING TO END CAPS

THEN SECURE END CAPS

TO THE ENDS OF J CAP.

 

J-CAP

SECURE J-CAP

END CAP

W/#14 S.M. SCREWS.

14

CAH-SVX01A-EN

Image 14
Contents Custom Climate Changer Air Handlers JulyCAH-SVX01A-EN Unit Description Protecting EnvironmentContents Controls Wiring Sizes ConnectionsOperating Environment Factory-Mounted ControlsUltraviolet UV Germicidal Irradiation Lights optional Job Site Storage Recommendations Receiving ChecklistResolving Shipping Damage Use Canvas OnlyLong-Term Storage Pre-Installation Requirements General StoragePreparing the Unit Site Outdoor Storage ConsiderationsRoof Curb Installation Typical Curb Installation ChecklistLifting and Rigging General Lifting ConsiderationsUnit Assembly Assembly HardwareTCP Model Assembly Instructions Joining Sections Edge-to- EdgeTCP Base Section Assembly Typical TCP base assemblyInstallation TCP Wall Section Assembly Typical TCP Outdoor Roof Section Assembly TypicalIndoor Roof Assembly Complete Installation TCP Indoor Roof Section Assembly TypicalBase to Wall Assembly Complete TCC Model Assembly Instructions Joining sections Edge to EdgeApply butyl tape to shipping splits Add caulk along the seam Join internal shipping split frame TCC wall sections assembly typical Installation TCC indoor roof sections assembly typicalInstallation TCC outdoor roof sections assembly typical Join outdoor roof panels at the seamsTrim roof joint strip Duct Connections Component Installation RequirementsIsolator Adjustment FansMagnahelic Air Filter Gage Traq DampersControl Dampers Installation Air Filters Front Load FiltersOutdoor Unit Weather Hoods Bag or Cartridge FiltersGeneral Recommendations Use a Backup WrenchCoil Piping Connections Prevent Coil DamageInstallation Drain Pan Trapping Water DamageInstallation Steam Coil Piping Coil DamageInstallation Water Coil Piping Typical piping for type 5W one-row water coilInstallation Refrigerant Coil Piping Liquid LinesValve Damage Type F refrigerant coil with packed elbowExamples of Field-Installed Evaporator Piping Single-circuit evaporator coil with one distributorSingle-circuit evaporator coil with two distributors Single-circuit evaporator coil with four distributors Dual-circuit evaporator coil with two distributors Dual-circuit evaporator coil with four distributors Dual-circuit evaporator coil with eight distributors Use Copper Conductors Only WiringHazardous Voltage with CapacitorsJunction box mounting and wiring details External Insulating RequirementsCoil-Related Checks Proper Water Treatment Pre-Startup ChecklistFan-Related Checks Motor-Related ChecksCalculate Motor Voltage Imbalance Unit OperationGeneral Checks Startup Tension the Fan Belt Tension Belts CorrectlyStartup Multibelt Check Determine Fan SpeedSheave Alignment Routine Maintenance Permanent Filters Air FiltersThrowaway Filters Front Load FiltersFans Inspecting and Cleaning FansDrain Pans Bearing Set Screw AlignmentFan Bearing Lubrication Fan Motor InspectionType K Cooling Coils CoilsSteam and Water Coils Refrigerant CoilsMoisture Purge Cycle Internal Insulation Replacement of ultraviolet bulbs Ultraviolet UV Germicidal Irradiation LightsTroubleshooting Alignment section on CAH-SVX01A-EN CAH-SVX01A-EN Trane