PB Heat Gas/Oil Boilers manual Connect Fuel Piping, General, Install Fuel OIL Piping

Page 33

CONNECT FUEL PIPING

7. CONNECT FUEL PIPING

A.GENERAL

1.Read the Burner Instruction Manual, supplied with the boiler or with the burner if purchased separately. Review applicable code requirements for burner and fuel piping installations.

2.Install piping to allow removal of burner and access to combustion chamber for cleaning or service.

B.INSTALL FUEL OIL PIPING

1.Place the fuel oil tank and install the piping in accordance with NFPA-31 and all other applicable codes.

2.General Guidelines for Oil Piping

a)Follow the guidelines in the Burner Manual for sizing oil lines. Never use smaller than 1/2" OD copper tubing.

b)Install manual shut-off valves on the suction line at the burner and at the oil line entrance to the building. If installing a shut-off valve on the return line, you must provide an oil pressure relief valve piped ahead of the shut-off valve and discharged to the tank to prevent over-pressure conditions.

c)Install a two-pipe oil distribution system when possible. It will improve the reliability of the oil delivery to the burner.

d)Use flare fittings when using copper tubing.

e)Provide an oil line filter in the suction line. Size the filter for the suction gear capacity of the burner oil pump if running a two-pipe system.

f)If burner is above the top of the fuel oil tank, install a check valve on the oil suction line at the burner to prevent oil from evacuating the line. If burner is below the top of the tank, install an anti-siphon device to prevent oil flow should the oil line break.

C.INSTALL GAS SUPPLY PIPING

1.Size the piping as required by the National Fuel Gas Code, ANSI Z223.1 or as required by local codes.

Figure 7.1: Gas Supply Connection to Boiler

4.Install a Service Valve, Sediment Trap and Ground Joint Union at the supply connection to the Gas Control Train as shown in Figure 7.1. These are not supplied with the boiler. Install them in accordance with local codes.

5.Use only pipe joint compounds rated for use with Liquefied Petroleum Gases.

D.TEST GAS SUPPLY PIPING

1.ISOLATE THE BOILER GAS CONTROL TRAIN FROM THE SYSTEM DURING TEST:

a)Test pressure 1/2 psig or less – Close the Manual Shut-Off Valve on the Boiler Gas Control Train.

b)Test pressure over 1/2 psig – Disconnect the gas supply piping upstream of the Boiler Manual Shut-Off Valve.

a)Use Table 7.1 for sizing of natural gas for a system pressure drop of 0.3 inch water column.

2.The standard gas train is designed for a maximum pressure of 1/2 psig (14 inches water column). Make sure the system regulator will not allow a higher pressure to the Gas Control Train under any conditions.

3.The minimum gas supply pressure is listed on the Burner Rating Plate. Make sure the system regulator and the piping are sized and adjusted properly to provide this pressure under all conditions.

WARNING

Do not expose the Gas Control Train to excessive pressure. The gas valves can be damaged. This could result in explosion hazard and severe personal injury or death.

Do not test gas supply piping with open flame. Use a soap suds mixture brushed onto the pipe joints to test for leaks.

31

Image 33
Contents Series LC/LCE Table of Contents Special Attention Boxes Using this ManualAccessibility Clearances PreinstallationClearance from Combustible Construction Combustion and Ventilation AIRChimney or Vent Foundation Layout Boiler SettingPlanning the Layout Installation SurveyVerify Components Foundation LengthsLwco 2A Series LC Shipping ListInterm Back 2B Series LCE Shipping ListStandard and Optional Jacket Cartons, Front/Back Panels Standard and Optional Sections for Knockdown BoilersStandard and Optional Jacket Cartons, Top/Side Panels 6A Burner Mounting Plates6B Burner Mounting Plates Trim CartonsControl Cartons Packaged Boiler Place the BoilerAssembled Block Boiler Knockdown BoilerApply Silcone Sealant Place the Boiler Series LC Boiler Assembly Right Side View Series LCE Boiler Assembly Right Side View Model Torque Specification/ProcedureLC/LCE Boiler Section Assembly Sequence Install Coils or Plates Hydrostatic Test the BoilerTankless Coil Ratings Install Flue Collar Apply Cleanout Cover PlatesInstall Chamber Liner Install Flue BafflesLow Return Temperature Piping, General LOW System TemperaturePipe the Boiler PreparationReturn Connections @ 20F Output RiseSize Header Variable Low Temperature Constant Low TemperatureMultiple Boiler Installations Chilled Water SystemsHigh Flow Rate Piping Piping for Variable Low Temperature Systems, Single Boiler Pipe the Boiler Pipe the Boiler Assemble the Jacket Jacket Assembly Install Burner Mounting Plate Install the BurnerVenting Burner ApplicationChamber Burner Front Plate Extension Past Jacket Inches Beckett Carlin Gordon Power Webster Inches PiattInstall GAS Supply Piping Install Fuel OIL PipingConnect Fuel Piping GeneralPipe Length PipeSpecific Gravity Multiply Capacity by Install Safety Relief Valve Install Controls and TrimInstall Drain Valve Install LOW Water CutoffsConnect Supply Wiring Install Control WiringPipe Tankless Heaters if Used Control and Pipe Tapping Locations Suggested Piping Single Tankless Coil Installation Check the Piping Starting the BoilerFill the Boiler RUN Burner CHECK-OUTCheck Boiler Controls Typical Combustion Chamber Pressure and Boiler Draft LossModel Combustion Chamber Pressure Boiler Draft Loss Maintenance Maintenance Annual Placing Boiler in OperationTo Shut Down the Boiler Daily Maintenance Monthly MaintenanceSeries LC/LCE Boiler Ratings Boiler Ratings & DimensionsSeries LC Dimensional Diagram Series LC/LCE Boiler Dimensions Series LC/LCE Boiler DimensionsSeries LC Boiler Assembly Repair PartsDescription Part Selection Information Stock Code 1A Series LC Repair Parts1B Series LC Repair Parts Series LCE Boiler Assembly 2A Series LCE Repair Parts 2B Series LCE Repair Parts Page Page Series LC/LCE