Frymaster H52 Series warranty Non-CE Standard For Incoming Gas Pressures

Page 9

5.Refer to the data plate on the inside of the fryer door to determine if the fryer burner is config- ured for the proper type of gas before connecting the fryer quick-disconnect device or piping from the gas supply line.

6.Verify the minimum and maximum gas supply pressures for the type of gas to be used in accor- dance with the accompanying tables.

CE Standard

for Incoming Gas Pressures

for Fryers Manufactured After April 1999

 

Pressure

Orifice Diameter

Regulator Pressure

 

 

Single

Dual

Single

Dual

Gas

(mbar)(1)

Vat

Vat

Vat

Vat

G20

20

2 x 3.40

2 x 3.40

7 mbar

6.5 mbar

 

G25

20 or 25

2 x 3.40

2 x 3.40

10 mbar

9 mbar

 

G30

28/30 or 50

2 x 2.05

2 x 2.05

17 mbar

17 mbar

 

G31

37 or 50

2 x 2.05

2 x 2.05

20 mbar

18.5 mbar

 

(1) mbar = 10.2 mm H2O

CE Standard

for Incoming Gas Pressures

for Fryers Manufactured Through April 1999

 

Pressure

Orifice Diameter

Regulator Pressure

 

 

Single

Dual

Single

Dual

Gas

(mbar)(1)

Vat

Vat

Vat

Vat

G20

20

2 x 3.40

2 x 3.40

7 mbar

6.5 mbar

 

G25

20 - 25

2 x 3.40

2 x 3.40

10 mbar

9 mbar

 

G31

37 - 50

2 x 2.05

2 x 2.05

20.2 mbar

18.5 mbar

 

(1) mbar = 10.2 mm H2O

Non-CE Standard

for Incoming Gas Pressures

Gas

Minimum

Maximum

 

6" W.C.

14" W.C.

Natural

1.49 kPa

3.48 kPa

 

14.93 mbar

34.84 mbar

 

11" W.C.

14" W.C.

LP

2.74 kPa

3.48 kPa

 

27.37 mbar

34.84 mbar

 

 

 

 

 

 

7.For fryers equipped with a FootPrint III system (BIH52 models), plug the electrical cord into a power receptacle behind the fryer.

2-4

Image 9
Contents OPERATOR’S Manual Frymaster H52 Series GAS Fryer Page General IntroductionComputer Information European Community CE Specific InformationWhat to do if your equipment arrives damaged Service Information General Installation Requirements Installation InstructionsNational Code Requirements Caster/Leg Installation Non-CE Standard For Incoming Gas Pressures Countries Categories GAS Connection to Gas LineCE Standard Gas Vat Converting to Another Gas TypeNon-CE Gas Conversion Kits CE Gas Conversion Kits for Units with Gas ValveFrypot Boil-Out Shutdown Operating Fryers With M100B Cooking ComputersDescription Introduction To The M-100B Cooking ComputerOperating the Computer on Full-Vat Fryers Viewing the Frypot Temperature Actual or Setpoint Operating the Computer on Split-Vat FryersCooking Product Full-Vat or Split-Vat Recovery Out of Range REC Lock M-100B Computer Problem Condition IndicatorsOpen Drain Valve Indication M-100B Computer Set-Up and Programming Instructions Probe Failure IndicationHow to Enter the Setup Mode 1 M-100B Computer Setup ModeHow to Change the Computer’s Display Language How to Configure the Computer for Use on a Gas FryerHow to Change Computer Product/Temperature Displays 2 M-100B Computer Programming Mode How to Activate or Deactivate the Frypot BOIL-OUT FeatureHow to Enter the Program Mode How to Reset the Computer to the Factory DefaultsHow to Change the Cooking Temperature Setpoint How to Enter a Product Name in a Test Menu How to Suppress a Shake, QA, or Duty Function How to Display the Product Cycle Accumulator Information How to Display Use Time InformationHow to Use the Filter Countdown Timer Introduction to the Analog Controller Operating Fryers With Analog ControllersC D E F G H I J K L M N Analog Controller High-Limit Check Page Filtering Operating the Built-In Filtration System Page Operating the Filter Unit Page Getting the Most Out of Your Filter Page Preventive Maintenance and Troubleshooting Preventive MaintenanceTroubleshooting REC Lock Troubleshooting Fryers with M100B ComputersIgnition Failure Display Remains Blank When ON/OFF Switches are Pressed Troubleshooting Fryers Equipped with Analog Controllers Did burners Troubleshooting Built-in Filtration System Pump does Not RUN