Gas Connection Pipe Sizes

(Minimum incoming pipe size should be 1 1/2" (38 mm))

 

 

 

 

4 or more

Gas

Single Unit

2 - 3 Units

 

units*

Natural

3/4" (19 mm)

1" (25 mm)

1

1/4" (33 mm)

Propane

1/2" (13 mm)

3/4" (19 mm)

 

1" (25 mm)

Manufactured

1" (25 mm)

1 1/4" (33 mm)

1

1/2" (38 mm)

*For distances of more than 20 feet (6 m) and/or more than 4 fittings or elbows, increase the con- nection by one pipe size.

Before connecting new pipe to your unit, the pipe must be thoroughly blown out to remove any for- eign particles. If these foreign particles get into the burner and controls, they will cause improper and sometimes dangerous operation.

CE Standard

Required airflow for the combustion air supply is 2m3/h per kW.

1.Connect the quick-disconnect hose to the fryer quick-disconnect fitting under the front of the fryer and to the building gas line.

NOTE: Some fryers are configured for a rigid connection to the gas supply line. These units are connected to the gas supply line at the rear of the unit.

When using thread compound, use very small amounts on male threads only. Use a pipe thread compound that is not affected by the chemical action of LP gases (Loctite™ PST56765 Sealant is one such compound). DO NOT apply compound to the first two threads. This will ensure that the burner orifices and control valve do not become clogged.

2.Open the gas supply to the fryer and check all piping, fittings, and gas connections for leaks. A soap solution should be used for this purpose.

DANGER

Never use matches, candles, or any other ignition source to check for leaks.

If gas odors are detected, shut off the gas supply to the fryer

at the main shut-off valve and contact the local gas company or an authorized

service agency for service.

3.Close the fryer drain valve and fill the frypot with water and boil-out solution to the bottom OIL- LEVEL line at the rear of the frypot. Light the fryer and perform the boil-out procedures that are described in the “Lighting Instructions” and “Boiling Out the Frypot” topics found in Chapter 3 of this manual.

2-6

Image 11
Contents OPERATOR’S Manual Frymaster H52 Series GAS Fryer Page General IntroductionWhat to do if your equipment arrives damaged Computer InformationEuropean Community CE Specific Information Service Information General Installation Requirements Installation InstructionsNational Code Requirements Caster/Leg Installation Non-CE Standard For Incoming Gas Pressures Countries Categories GAS Connection to Gas LineCE Standard Gas Vat Converting to Another Gas TypeFrypot Boil-Out Non-CE Gas Conversion KitsCE Gas Conversion Kits for Units with Gas Valve Shutdown Operating Fryers With M100B Cooking ComputersDescription Introduction To The M-100B Cooking ComputerOperating the Computer on Full-Vat Fryers Cooking Product Full-Vat or Split-Vat Viewing the Frypot Temperature Actual or SetpointOperating the Computer on Split-Vat Fryers Recovery Out of Range REC Lock M-100B Computer Problem Condition IndicatorsOpen Drain Valve Indication M-100B Computer Set-Up and Programming Instructions Probe Failure IndicationHow to Configure the Computer for Use on a Gas Fryer 1 M-100B Computer Setup ModeHow to Enter the Setup Mode How to Change the Computer’s Display LanguageHow to Change Computer Product/Temperature Displays How to Reset the Computer to the Factory Defaults How to Activate or Deactivate the Frypot BOIL-OUT Feature2 M-100B Computer Programming Mode How to Enter the Program ModeHow to Change the Cooking Temperature Setpoint How to Enter a Product Name in a Test Menu How to Suppress a Shake, QA, or Duty Function How to Display the Product Cycle Accumulator Information How to Display Use Time InformationHow to Use the Filter Countdown Timer Introduction to the Analog Controller Operating Fryers With Analog ControllersC D E F G H I J K L M N Analog Controller High-Limit Check Page Filtering Operating the Built-In Filtration System Page Operating the Filter Unit Page Getting the Most Out of Your Filter Page Troubleshooting Preventive Maintenance and TroubleshootingPreventive Maintenance REC Lock Troubleshooting Fryers with M100B ComputersIgnition Failure Display Remains Blank When ON/OFF Switches are Pressed Troubleshooting Fryers Equipped with Analog Controllers Did burners Troubleshooting Built-in Filtration System Pump does Not RUN