Operator Interface
Diagnostic Screen
The diagnostic screen is accessible by touching the Alarms enunciator.
When an alarm is present, the alarm enunciator is present next to the Stop key. A flashing “alarm” indicates a machine shutdown and a non flashing “alarm” indicates an informational message.
Machine shutdowns can be of two types:
Latching - Machine Shutdown Manual Reset Required (MMR)
or
Latching (MMR) require corrective action and manual reset.
There are over 200 potential messages, too numerous to incorporate in this manual.
Up to ten active diagnostics can be displayed if required.
The reason for all diagnostics must be determined and corrected. Do not reset and restart the chiller as this can cause a repeat failure. Contact local Trane Service for assistance as necessary.
After corrective action, the chiller can be reset and/or restarted. In the case of “Unit Shutdown - Reset Required” diagnostic types, the chiller will have to be manually reset through the Diagnostics alarm menu.
When reset they become historic and viewable via the service tool TechView.
Performing a Reset All Active Diagnostics will reset all active diagnostics regardless of type, machine or refrigerant circuit.
A Manual Override indicator (shares space with the Alarms key) alerts the operator to the presence of a manual override. An Alarm will take precedence over any manual override, until the reset of active alarms, at which point the Manual indicator would reappear if such an override exists.
Temperature settings can be expressed in F or C, depending on Display Units settings.
Dashes (“- - -
The languages for DynaView™ will reside in the main processor. The main processor will hold three languages, English, and two alternate languages. The service tool (TechView™) will load the main processor with user selected languages from a list of available translations. Whenever possible, complete words will be used on the persistent keys as described.
37 |