Control System
Components
GBAS (Generic Building Automation System)
1A15 Optional Dual | GBAS | Signal #1 | Percent RLA Compressor Output | |
Analog Input/ |
|
|
|
|
output Module |
|
|
|
|
1A16 Optional Dual | GBAS | Signal #1 | External Current limit Setpoint | |
Analog Input/ |
|
|
|
|
output Module |
|
|
|
|
1A16 Optional Dual | GBAS | Signal #2 | Chilled Water Reset input, | |
Analog Input/ |
|
| or External Chiller Water Setpoint |
|
output Module |
|
|
|
|
Percent RLA Output
2 to 10 Vdc corresponding to 0 to
120% RLA. With a resolution of 0.146%. The Percent RLA Output connections are on the terminals 1A15
The following graph illustrates the output:
Figure 27. Voltage versus percent RLA