Operator Interface
The active chilled water setpoint is the setpoint that is currently in use. It will be displayed to 0.1 degrees Fahrenheit or Celsius. Touching the double arrow to the left of the Active Chilled Water Setpoint will take the user to the active chilled water setpoint arbitration
The Active Chilled Water Setpoint the result of arbitration between the front panel, BAS, and external setpoints,
The chilled water reset status area in the right most column will display one of the following messages: Return, Constant Return, Outdoor, None
The left column text “Front Panel”, “BAS”, “External”, Chilled Water Reset, and “Active Chilled Water Setpoint” will always be present regardless of installation or enabling those optional items. In the second column “- - -
The “Back” button provides navigation back to the chiller screen.
38 |