Machine Protection
and Adaptive
Control
Table 3. Values for start reset types
The values for “RESET TYPE” are:
Reset |
| Outdoor | Return | Const Return |
Type: | Disable | Air Reset | Reset | Reset |
|
| |||
The values for “RESET RATIO” for each of the reset types are: |
| |||
Reset | Reset | Increment | Increment | Factory |
Type | Ratio | English | SI Units | Default |
| Range | Units |
| Value |
Return | 10 to 120 percent | 1 percent | 1 percent | 50 percent |
Outdoor | 1 percent | 1 percent | 10 percent | |
|
| |||
The values for “START RESET “ for each of the reset types are: |
| |||
Reset | Start | Increment | Increment | Factory |
Type | Reset | English | SI Units | Default |
| Range | Units |
| Value |
Return | 4 to 30°F | 0.1°F | 0.1°C | 10°F (5.6°C) |
| (2.2 to 16.7°C) |
|
|
|
Outdoor | 50 to 130°F | 0.1°F | 0.1°C | 90°F |
| (10 to 54.44°C) |
|
| (32.22°C) |
The values for “MAXIMUM RESET” for each of the reset types are: | ||||
Reset | Maximum | Increment | Increment | Factory |
| Reset | English | SI Units | Default |
| Range | Units |
| Value |
Return | 0 to 20°F | 0.1°F | 0.1°C | 5°F |
| (0.0 to 11.11°C) |
|
| (2.78°C) |
Outdoor | 0 to 20°F | 0.1°F | 0.1°C | 5°F |
| (0.2 to 11.11°C) |
|
| (2.78°C) |
Constant Return
CWS’ = CWS + 100 percent (Design Delta Temperature) - (TWE- TWL) and CWS’ > or = CWS and CWS’
Notice that Constant Return is nothing more than a specific case of Return Reset offered for operator convenience.
When any type of CWR is enabled, the UCP will step the CWS toward the desired CWS (based on the above equations and setup parameters) at a rate of 1°F every 5 minutes until the Active CWS equals the desired CWS’. This applies when the chiller is running only.
Using the Equation for calculating CWR for Outdoor Air Temperature
Equation:
Degrees of Reset = Reset Ratio*(Start Reset - TOD)
The chiller will start at the Differential to Start value above a fully reset CWS or CWS for both Return and Outdoor Reset.
The graph on the next page, shows the reset function for Outdoor Air Temperature: Note: This graph assumes that Maximum Reset is set to 20 degrees.
Degrees of Reset:
Degrees of Reset = Active CWS - Front Panel CWS
or
Degrees of Reset = CWS’ - CWS
To obtain Active CWS from Degrees of Reset: Active CWS = Degrees of Reset + Front Panel CWS
(* = multiply)