American Standard CH530 manual Control Panel Devices

Page 54

Control System

Components

Control Panel Devices

Standard Devices

 

Controls

 

 

Field Connection

Description

Package

 

Purpose

Point Terminals

1A1 Power Supply

Standard

#1

Converts 24 vac to 24 vdc

not for field use

1A2 Power Supply

(as required)

#2

Converts 24 vac to 24 vdc

not for field use

1A3 Dual Relay

Standard

Relay #1

Oil Heater Relay

not for field use

Output modules

 

 

 

 

1A4 Dual High

Standard

 

High Pressure Cutout

not for field use

Voltage Input

 

 

 

 

1A5 Quad Relay

Standard

Relay #1

Chilled water pump

J2-4 NO, J2-5 NC,

Output modules

 

 

(Relay #1)

J2-6 common

1A5 Quad Relay

Standard

Relay #2

Condenser water pump control

J2-1 NO, J2-2 NC,

Output modules

 

 

(relay #2)

J2-3 common

1A6 Dual High

Standard

Input 1

Condenser Flow Input

J2-2 Condenser water

Voltage Input

 

 

 

flow switch

1A6 Dual High

Standard

Input 2

Evaporator Flow Input

J3-2 Chilled water

Voltage Input

 

 

 

flow switch

1A7 High Power

Standard

 

Oil Pump and

not for field use

Output Relay

 

 

Refrigerant Pump

 

1A13 Dual LV Binary

Standard

Signal #1

External Auto Stop,

J2-1 Binary Input Signal #1,

input module

 

 

 

J2-2 Ground

1A13 Dual LV Binary

Standard

Signal #2

Emergency stop

J2-3 Binary Input Signal #2,

input module

 

 

 

J2-4 Ground

1A26 Temp Sensor

Standard

 

Compressor Motor

not for field use

Input

 

 

 

 

1F1

Standard

 

LLID Power Supply Transformer

not for field use

 

 

 

Primary Circuit protection

 

1T1

Standard

 

Control Panel Power

not for field use

 

 

 

Transformer ; 120:24Vac

 

1Q1

Standard

 

Circuit Breaker Compressor

not for field use

 

 

 

Motor Controller Control Power

 

 

 

 

Branch Circuit

 

1Q2

Standard

 

Circuit Breaker -

not for field use

 

 

 

Purge System Branch Circuit

 

1Q3

Standard

 

Circuit Breaker –

not for field use

 

 

 

Module [- LLID]

 

 

 

 

Power Supply Branch Circuit

 

1Q4

Standard

 

Circuit Breaker -

not for field use

 

 

 

Oil System Control

 

 

 

 

Branch Circuit

 

1Q5

Standard

 

Oil Pump Motor Branch

not for field use

 

 

 

Circuit protection

 

1X1 Terminal Block

Standard

 

Control Panel Terminal Block,

1X1-5 Chilled water flow

 

 

 

Flow switch connections

flow switch input

 

 

 

 

1X1-6 Condenser water flow

 

 

 

 

switch input

54

CDHF-SVU01C-EN

Image 54
Contents X39640670030CDHF-SVU01C-EN Read these carefully Contents About this manual General InformationLiterature change Unit NameplateGeneral Information = 560 3 stage 935 2 stage Y = 500 3 stage 835 2 stage Commonly Used Acronyms Control Optional PackagesOverview General Duplex unit components front viewGeneral Duplex unit components 2 stage compressor Cooling Cycle Compressor 1 or 2 2 StagePressure enthalpy curve 3 stage compressor Pressure enthalpy curve 2 stage compressor TechView Chiller Service Tool DynaView Human InterfaceSoftware States Figure Power Up DiagramSoftware Operation Overview Diagram Timeline Text FiguresCDHE/F/G sequence of operation auto to running Staging Second Compressor OnStaging Second Compressor Off Satisfied SetpointCDHF/G sequence of operation lead 1/lag Fixed Sequence Compressor 2 / Compressor CDHE/F/G sequence of operation lead 2 lagSequencing Balanced Starts and Hours CDHF/G sequence of operation equalize starts and hoursSimultaneous Compressor Start/ Stop CDHF/G sequence of operation combined startRestart Inhibit Free Starts Restart Inhibit Start to Start Time SettingRestart Inhibit Clear Restart InhibitSurface Temperatures Oil and Refrigerant PumpOil refrigerant pump circuit 1 or Base Loading Control Algorithm 20 100 percent RLAGeneral Information Ice Machine Control Sequence of operation ice making running to ice makingHot Water control Unit Control Panel UCP Control Panel Devices and Unit Mounted DevicesUnit Control Panel UCP Variable water flow through the evaporator User-defined language supportOperator Interface DynaView main processorOperator Interface Chiller Stop Prevention/Inhibit Feature How It WorksTop Level Mode Description System Reset Reference Main Screen Chiller Operating ModeCircuit Operating Mode Main Screen Data Fields TableDiagnostic Screen Back button provides navigation back to the chiller screen Operator Interface Report Menu ReportsReport name System Condenser Report name System EvaporatorReport name Circuit Evaporator Report name Circuit CondenserHistoric Diagnostics Log Report name System Ashrae Chiller LogSetting Tab screens provides a user Header ScreenFeature Settings ChillerDisplay Settings System Mode OverridesCircuit Mode Overrides PurgeOperator Interface Operator Interface Operator Interface Operator Interface Operator Interface IPC3 Definitions Bus Management Interprocessor CommunicationInter Processor Communications IPC3 BindingControl System Components Control panel components layoutControl System Components Control Panel Devices Maximum Capacity Relay Machine Shutdown Manual Reset MMRHead Relief Request Output Compressor Running RelayRefrigerant Monitor Input 1A17 ExopTrmm TRM4 Tracer Comm 4 interface Cdrp Condenser Refrigerant Pressure OutputEpro Enhanced Protection Condenser Pressure Output Temperature basedCdrp Refrigerant Pressure Output Option 1A15 Pressure basedRefrigerant Differential Pressure Indication Output Gbas Generic Building Automation System Percent RLA OutputExternal Current Limit Setpoint Module CharacteristicsExternal Chilled Water Setpoint Ecws Wpsr WFC Water Pressure Sensing Option1A8, 1A9, 1A11, 1A12 Quad Relay Output Status 1A13, 1A18, 1A19, 1A20 Dual Binary input module1A14 Communication interface Module Recommended Length to Run external Output signals 1A15, 1A16, 1A17, 1A21 Dual Analog Input/output ModuleAnalog Input Unit mounted devices Control System Components Control System Components Control Sequence of Operation Electrical SequenceUCP and Wye-Delta Starter Control Circuits Delay time 200 msec. Opens 2K1 Control Sequence of Operation Control Sequence Operation Test and start timing sequenceAFD Momentary Power Loss MPL Protection Machine Protection Adaptive ControlCurrent Overload Protection Overload trip time versus percent RLAPhase Loss Protection Current Limit ProtectionReverse Rotation Protection Differential to Start or Stop SoftLoadingMinimum and Maximum Capacity Limit Leaving Water Temperature Cutout Evaporator LimitLow Refrigerant Temperature Cutout Head Relief RelayCutout strategy Condenser Limit Restart Inhibit High Vacuum Lockout Oil Temperature Control Maximum Reset Controls Chilled Water Reset CWROutdoor Air Temperature Return WaterConstant Return Values for start reset typesDegrees of Reset EquationReset Ratio Outdoor air temperature versus degrees of resetReset function for return CWR Reset Ratio = 50% Return CWR Unit Start-Up Procedures Unit StartupDaily Unit Start-Up Seasonal Unit Start-Up Live Electrical ComponentsToxic Hazards ModeOil Pump Heater Operation Unit Shutdown ProceduresUnit Shutdown Seasonal Unit ShutdownMoisture Contamination Periodic MaintenanceDaily Maintenance and Checks Record Keeping FormsHazardous Voltage w/Capacitors Weekly MaintenanceNormal Chiller Operating Characteristics Every 3 MonthsOff-Season Maintenance Annual MaintenanceHeater Damage Oil MaintenanceOil Change Procedure Compressor Oil ChangeOil Filter Replacement Replacing Oil FilterOther Maintenance Requirements MaintenanceOil Supply System Problems Hazardous Voltage w/ CapacitorsRotary valve in drain position Front View with Refrigerant PumpContains Refrigerant Refrigerant ChargeCleaning the Condenser Recovery and Recycle ConnectionsLeak Testing Proper Water TreatmentCleaning the Evaporator Control Settings AdjustmentsUnit Corrosion Damage Purge System Unit Preparation103 104 105 106 107 108 109 110 111 112 113 114 115 Trane