American Standard CH530 Machine Protection Adaptive Control, Momentary Power Loss MPL Protection

Page 72

Machine Protection

and Adaptive

Control

Momentary Power Loss (MPL) Protection.

Improved power measurement and protection algorithms allow the unit to accommodate more power anomalies than ever. If the chiller must shut down, faster restarts get the machine up and running as soon as possible.

Momentary power loss (MPL) detects the existence of a power loss to the compressor motor and responds by initiating the disconnection of the compressor motor from the power source. Power interruptions of less than 30 line-cycles are defined as momentary power losses. Tests have shown that these short-term power

interruptions can be damaging to the motor and compressor if the chiller is reconnected to the line while the motor and line phases do not match. The chiller will be shut down when a MPL is detected and will display a non-latching diagnostic indicating the failure. The oil pump will be run for the post-lube time period when power returns. The compressor and compressor motor are protected from damage from large torques and inrush currents resulting from reconnecting the compressor motor to the power source following a momentary loss of power.

MPL’s greater than 2 or 3 cycles are detected resulting in unit shut down. Disconnection from the line is initiated within 6 line cycles of the power loss. MPL protection is active anytime the compressor is in the running mode. (The transition complete input has been satisfied).

MPL is enabled however can be disabled, if required via the service tool.

Figure 29. Sequence of operation: momentary power loss, (DynaViewand starter module remain powered)

Enforce Stop to Start Timer

(5 to 200 Seconds 7 Sec is Default)

72

CDHF-SVU01C-EN

Image 72
Contents X39640670030CDHF-SVU01C-EN Read these carefully Contents General Information Literature changeAbout this manual Unit NameplateGeneral Information = 560 3 stage 935 2 stage Y = 500 3 stage 835 2 stage Commonly Used Acronyms Control Optional PackagesOverview General Duplex unit components front viewGeneral Duplex unit components 2 stage compressor Cooling Cycle Compressor 1 or 2 2 StagePressure enthalpy curve 3 stage compressor Pressure enthalpy curve 2 stage compressor TechView Chiller Service Tool DynaView Human InterfacePower Up Diagram Software Operation Overview DiagramSoftware States Figure Timeline Text FiguresCDHE/F/G sequence of operation auto to running Staging Second Compressor OnStaging Second Compressor Off Satisfied SetpointCDHF/G sequence of operation lead 1/lag Fixed Sequence Compressor 2 / Compressor CDHE/F/G sequence of operation lead 2 lagSequencing Balanced Starts and Hours CDHF/G sequence of operation equalize starts and hoursSimultaneous Compressor Start/ Stop CDHF/G sequence of operation combined startRestart Inhibit Start to Start Time Setting Restart InhibitRestart Inhibit Free Starts Clear Restart InhibitSurface Temperatures Oil and Refrigerant PumpOil refrigerant pump circuit 1 or Base Loading Control Algorithm 20 100 percent RLAGeneral Information Ice Machine Control Sequence of operation ice making running to ice makingHot Water control Unit Control Panel UCP Control Panel Devices and Unit Mounted DevicesUnit Control Panel UCP Variable water flow through the evaporator User-defined language supportOperator Interface DynaView main processorOperator Interface Chiller Stop Prevention/Inhibit Feature How It WorksTop Level Mode Description System Reset Reference Chiller Operating Mode Circuit Operating ModeMain Screen Main Screen Data Fields TableDiagnostic Screen Back button provides navigation back to the chiller screen Operator Interface Report Menu ReportsReport name System Evaporator Report name Circuit EvaporatorReport name System Condenser Report name Circuit CondenserHistoric Diagnostics Log Report name System Ashrae Chiller LogSetting Tab screens provides a user Header ScreenFeature Settings ChillerSystem Mode Overrides Circuit Mode OverridesDisplay Settings PurgeOperator Interface Operator Interface Operator Interface Operator Interface Operator Interface Interprocessor Communication Inter Processor Communications IPC3IPC3 Definitions Bus Management BindingControl System Components Control panel components layoutControl System Components Control Panel Devices Machine Shutdown Manual Reset MMR Head Relief Request OutputMaximum Capacity Relay Compressor Running RelayRefrigerant Monitor Input 1A17 ExopTrmm TRM4 Tracer Comm 4 interface Cdrp Condenser Refrigerant Pressure OutputEpro Enhanced Protection Temperature based Cdrp Refrigerant Pressure Output Option 1A15Condenser Pressure Output Pressure basedRefrigerant Differential Pressure Indication Output Gbas Generic Building Automation System Percent RLA OutputModule Characteristics External Chilled Water Setpoint EcwsExternal Current Limit Setpoint Wpsr WFC Water Pressure Sensing Option1A8, 1A9, 1A11, 1A12 Quad Relay Output Status 1A13, 1A18, 1A19, 1A20 Dual Binary input module1A14 Communication interface Module Recommended Length to Run external Output signals 1A15, 1A16, 1A17, 1A21 Dual Analog Input/output ModuleAnalog Input Unit mounted devices Control System Components Control System Components Control Sequence of Operation Electrical SequenceUCP and Wye-Delta Starter Control Circuits Delay time 200 msec. Opens 2K1 Control Sequence of Operation Control Sequence Operation Test and start timing sequenceAFD Momentary Power Loss MPL Protection Machine Protection Adaptive ControlCurrent Overload Protection Overload trip time versus percent RLAPhase Loss Protection Current Limit ProtectionReverse Rotation Protection Differential to Start or Stop SoftLoadingMinimum and Maximum Capacity Limit Leaving Water Temperature Cutout Evaporator LimitLow Refrigerant Temperature Cutout Head Relief RelayCutout strategy Condenser Limit Restart Inhibit High Vacuum Lockout Oil Temperature Control Controls Chilled Water Reset CWR Outdoor Air TemperatureMaximum Reset Return WaterValues for start reset types Degrees of ResetConstant Return EquationReset Ratio Outdoor air temperature versus degrees of resetReset function for return CWR Reset Ratio = 50% Return CWR Unit Start-Up Procedures Unit StartupDaily Unit Start-Up Live Electrical Components Toxic HazardsSeasonal Unit Start-Up ModeUnit Shutdown Procedures Unit ShutdownOil Pump Heater Operation Seasonal Unit ShutdownPeriodic Maintenance Daily Maintenance and ChecksMoisture Contamination Record Keeping FormsWeekly Maintenance Normal Chiller Operating CharacteristicsHazardous Voltage w/Capacitors Every 3 MonthsOff-Season Maintenance Annual MaintenanceOil Maintenance Oil Change ProcedureHeater Damage Compressor Oil ChangeOil Filter Replacement Replacing Oil FilterMaintenance Oil Supply System ProblemsOther Maintenance Requirements Hazardous Voltage w/ CapacitorsRotary valve in drain position Front View with Refrigerant PumpContains Refrigerant Refrigerant ChargeRecovery and Recycle Connections Leak TestingCleaning the Condenser Proper Water TreatmentCleaning the Evaporator Control Settings AdjustmentsUnit Corrosion Damage Purge System Unit Preparation103 104 105 106 107 108 109 110 111 112 113 114 115 Trane