American Standard CH530 manual Purge System, Unit Preparation

Page 102

Maintenance

Purge System

Because some sections of the chiller’s refrigeration system operate at less-than-atmospheric pressure, the possibility exists that air and moisture may leak into the system. If allowed to accumulate, these noncondensables become trapped in the condenser; this increases condensing pressure and compressor power requirements, and reduces the chiller’s efficiency and cooling capacity.

The Trane EarthWise Purge is the only purge system available for the chiller. The purge is designed to remove noncondensable gases and water from the refrigeration system. EarthWise Purge unit operation, maintenance and trouble shooting is covered by a separate operation and maintenance manual, which may be obtained from the nearest Trane office.

Overview

This section describes extended storage requirements for installed chillers to be removed from service for an undetermined length of time.

Unit Preparation

The following steps are necessary in order to properly prepare a unit for storage.

1.Remove all liquid refrigerant if the unit is charged.

￿WARNING

Contains Refrigerant!

System contains oil and refrigerant and may be under positive pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.

Failure to follow proper procedures or the use of non-approved refrigerants, refrigerant substitutes, or refrigerant additives could result in death or serious injury or equipment damage.

2.After the liquid refrigerant is removed, using a recovery or recycle unit or vacuum pump, pull a vacuum to remove remaining refrigerant vapor from the unit.

3.After all traces of refrigerant are out of the unit, a positive nitrogen charge should be put into the unit (6 to 8 psig). This positive pressure must be checked monthly to insure no noncondensables get into the unit. Use a pressure gage on the evaporator shell to verify that the 6 to 8 psig dry nitrogen holding charge is still in the chiller. If this charge has escaped, contact a qualified service organization and the Trane sales engineer that handled the order.

4.The refrigerant charge should be stored in proper refrigerant containers. Due to possible leakage, do not store in used drums.

5.Maintain control power to the control panel. This will maintain oil temperature in the oil sump and the capability of the control panel to present report information. The Chiller Reports should be viewed once a week for normal readings. Any abnormal observation must be reported to the Trane Sales Engineer that handled the order.

102

CDHF-SVU01C-EN

Image 102
Contents X39640670030CDHF-SVU01C-EN Read these carefully Contents About this manual General InformationLiterature change Unit NameplateGeneral Information = 560 3 stage 935 2 stage Y = 500 3 stage 835 2 stage Commonly Used Acronyms Control Optional PackagesOverview General Duplex unit components front viewGeneral Duplex unit components 2 stage compressor Cooling Cycle Compressor 1 or 2 2 StagePressure enthalpy curve 3 stage compressor Pressure enthalpy curve 2 stage compressor TechView Chiller Service Tool DynaView Human InterfaceSoftware States Figure Power Up DiagramSoftware Operation Overview Diagram Timeline Text FiguresCDHE/F/G sequence of operation auto to running Staging Second Compressor OnStaging Second Compressor Off Satisfied SetpointCDHF/G sequence of operation lead 1/lag Fixed Sequence Compressor 2 / Compressor CDHE/F/G sequence of operation lead 2 lagSequencing Balanced Starts and Hours CDHF/G sequence of operation equalize starts and hoursSimultaneous Compressor Start/ Stop CDHF/G sequence of operation combined startRestart Inhibit Free Starts Restart Inhibit Start to Start Time SettingRestart Inhibit Clear Restart InhibitSurface Temperatures Oil and Refrigerant PumpOil refrigerant pump circuit 1 or Base Loading Control Algorithm 20 100 percent RLAGeneral Information Ice Machine Control Sequence of operation ice making running to ice makingHot Water control Unit Control Panel UCP Control Panel Devices and Unit Mounted DevicesUnit Control Panel UCP Variable water flow through the evaporator User-defined language supportOperator Interface DynaView main processorOperator Interface Chiller Stop Prevention/Inhibit Feature How It WorksTop Level Mode Description System Reset Reference Main Screen Chiller Operating ModeCircuit Operating Mode Main Screen Data Fields TableDiagnostic Screen Back button provides navigation back to the chiller screen Operator Interface Report Menu ReportsReport name System Condenser Report name System EvaporatorReport name Circuit Evaporator Report name Circuit CondenserHistoric Diagnostics Log Report name System Ashrae Chiller LogSetting Tab screens provides a user Header ScreenFeature Settings ChillerDisplay Settings System Mode OverridesCircuit Mode Overrides PurgeOperator Interface Operator Interface Operator Interface Operator Interface Operator Interface IPC3 Definitions Bus Management Interprocessor CommunicationInter Processor Communications IPC3 BindingControl System Components Control panel components layoutControl System Components Control Panel Devices Maximum Capacity Relay Machine Shutdown Manual Reset MMRHead Relief Request Output Compressor Running RelayRefrigerant Monitor Input 1A17 ExopTrmm TRM4 Tracer Comm 4 interface Cdrp Condenser Refrigerant Pressure OutputEpro Enhanced Protection Condenser Pressure Output Temperature basedCdrp Refrigerant Pressure Output Option 1A15 Pressure basedRefrigerant Differential Pressure Indication Output Gbas Generic Building Automation System Percent RLA OutputExternal Current Limit Setpoint Module CharacteristicsExternal Chilled Water Setpoint Ecws Wpsr WFC Water Pressure Sensing Option1A8, 1A9, 1A11, 1A12 Quad Relay Output Status 1A13, 1A18, 1A19, 1A20 Dual Binary input module1A14 Communication interface Module Recommended Length to Run external Output signals 1A15, 1A16, 1A17, 1A21 Dual Analog Input/output ModuleAnalog Input Unit mounted devices Control System Components Control System Components Control Sequence of Operation Electrical SequenceUCP and Wye-Delta Starter Control Circuits Delay time 200 msec. Opens 2K1 Control Sequence of Operation Control Sequence Operation Test and start timing sequenceAFD Momentary Power Loss MPL Protection Machine Protection Adaptive ControlCurrent Overload Protection Overload trip time versus percent RLAPhase Loss Protection Current Limit ProtectionReverse Rotation Protection Differential to Start or Stop SoftLoadingMinimum and Maximum Capacity Limit Leaving Water Temperature Cutout Evaporator LimitLow Refrigerant Temperature Cutout Head Relief RelayCutout strategy Condenser Limit Restart Inhibit High Vacuum Lockout Oil Temperature Control Maximum Reset Controls Chilled Water Reset CWROutdoor Air Temperature Return WaterConstant Return Values for start reset typesDegrees of Reset EquationReset Ratio Outdoor air temperature versus degrees of resetReset function for return CWR Reset Ratio = 50% Return CWR Unit Start-Up Procedures Unit StartupDaily Unit Start-Up Seasonal Unit Start-Up Live Electrical ComponentsToxic Hazards ModeOil Pump Heater Operation Unit Shutdown ProceduresUnit Shutdown Seasonal Unit ShutdownMoisture Contamination Periodic MaintenanceDaily Maintenance and Checks Record Keeping FormsHazardous Voltage w/Capacitors Weekly MaintenanceNormal Chiller Operating Characteristics Every 3 MonthsOff-Season Maintenance Annual MaintenanceHeater Damage Oil MaintenanceOil Change Procedure Compressor Oil ChangeOil Filter Replacement Replacing Oil FilterOther Maintenance Requirements MaintenanceOil Supply System Problems Hazardous Voltage w/ CapacitorsRotary valve in drain position Front View with Refrigerant PumpContains Refrigerant Refrigerant ChargeCleaning the Condenser Recovery and Recycle ConnectionsLeak Testing Proper Water TreatmentCleaning the Evaporator Control Settings AdjustmentsUnit Corrosion Damage Purge System Unit Preparation103 104 105 106 107 108 109 110 111 112 113 114 115 Trane