Control System Components
B)Refrigerant Differential Pressure Indication Output:
A 2 to 10 VDC analog output is provided instead of the previous condenser pressure output signal. This signal corresponds to a predetermined minimum and maximum pressure settings setup at commissioning of this feature. This relationship can be altered using the service tool if required.
The “Minimum Delta Pressure “ is typically set to 0 psi and will then correspond to 2 vdc. The “Maximum Delta Pressure “ is typically set to 30 psi and corresponds to 10 vdc.
The Minimum Delta Pressure Calibration setting has a range of 0- 400 psid
increments of 1 psid (1kPa). The condenser refrigerant pressure is based on the Condenser Refrigerant Temperature sensor if the Condenser Pressure Option is selected as “Not Installed” at the display.
The evaporator refrigerant pressure is based on the Saturated Evaporator Refrigerant Temperature Sensor.
See
Figure 26. Delta pressure setting - differential pressure based output (Defaults shown)
Note: In this example, 2 vdc corresponds to OPSI differential and 10 vdc corresponds to 30 psi differential. The minimum value of 0 psi, and maximum value of 30 psi are individually adjustable via the service tool.
59 |