American Standard CH530 manual Chiller, Feature Settings

Page 44

Operator

Interface

Chiller

Description

Resolution or (Enumerations), Default

Units

1. Front Panel Control Type

(Chilled Water, Hot Water), Chilled Water

Enum

2. Front Panel Chilled Water Setpt

(3)

 

 

+ or – XXX.X

Temperature

3. Front Panel Hot Water Setpt

(3)

 

 

+ or – XXX.X

Temperature

4. Front Panel Current Limit Setpt

XXX (4)

Percent RLA

5. Front Panel Base Load Cmd

On/Auto

enum

6. Front Panel Base Load Setpt

XXX

Percent

7. Front Panel Ice Build Cmd

On/Auto

Enum

8. Front Panel Ice Termn Setpt

XXX.X

Temperature

9. Ice to Normal Cool Timer Setpt

(0-10), 5 min

Minutes

10. Differential to Start

XXX.X

Temperature

11. Differential to Stop

XXX.X

Temperature

12. Setpoint Source

*(BAS/Ext/FP, Ext/ Front Panel, Front Panel),

 

 

BAS/Ext/FP Default

Enum

*Follows hierarchy of selection from left to right (except for ice building which is “OR” logic).

Feature Settings

Description

Resolution or (Enumerations), Default

Units

1. Chilled Water Reset

(Constant, Outdoor, Return, Disable), Disable

Enum

2. Return Reset Ratio

XXX

Percent

3. Return Start Reset

XXX.X

Temperature

4. Return Maximum Reset

XXX.X

Temperature

5. Outdoor Reset Ratio

XXX

Percent

6. Outdoor Start Reset

XXX.X

Temperature

7. Outdoor Maximum Reset

XXX.X

Temperature

8. Ext Chilled Water Setpoint

(Enable, Disable), Disable

Enum

9. Ext Current Limit Setpoint

(Enable, Disable), Disable

Enum

10. Ice Building Feature Enable

(Enable, Disable), Disable

Enum

11. Ext Base Loading Setpoint

(Enable, Disable), Disable

Enum

44

CDHF-SVU01C-EN

Image 44
Contents X39640670030CDHF-SVU01C-EN Read these carefully Contents General Information Literature changeAbout this manual Unit NameplateGeneral Information = 560 3 stage 935 2 stage Y = 500 3 stage 835 2 stage Commonly Used Acronyms Control Optional PackagesOverview General Duplex unit components front viewGeneral Duplex unit components 2 stage compressor Cooling Cycle Compressor 1 or 2 2 StagePressure enthalpy curve 3 stage compressor Pressure enthalpy curve 2 stage compressor TechView Chiller Service Tool DynaView Human InterfacePower Up Diagram Software Operation Overview DiagramSoftware States Figure Timeline Text FiguresCDHE/F/G sequence of operation auto to running Staging Second Compressor OnStaging Second Compressor Off Satisfied SetpointCDHF/G sequence of operation lead 1/lag Fixed Sequence Compressor 2 / Compressor CDHE/F/G sequence of operation lead 2 lagSequencing Balanced Starts and Hours CDHF/G sequence of operation equalize starts and hoursSimultaneous Compressor Start/ Stop CDHF/G sequence of operation combined startRestart Inhibit Start to Start Time Setting Restart InhibitRestart Inhibit Free Starts Clear Restart InhibitSurface Temperatures Oil and Refrigerant PumpOil refrigerant pump circuit 1 or Base Loading Control Algorithm 20 100 percent RLAGeneral Information Ice Machine Control Sequence of operation ice making running to ice makingHot Water control Unit Control Panel UCP Unit Control Panel UCPControl Panel Devices and Unit Mounted Devices Variable water flow through the evaporator User-defined language supportOperator Interface DynaView main processorOperator Interface Chiller Stop Prevention/Inhibit Feature How It WorksTop Level Mode Description System Reset Reference Chiller Operating Mode Circuit Operating ModeMain Screen Main Screen Data Fields TableDiagnostic Screen Back button provides navigation back to the chiller screen Operator Interface Report Menu ReportsReport name System Evaporator Report name Circuit EvaporatorReport name System Condenser Report name Circuit CondenserHistoric Diagnostics Log Report name System Ashrae Chiller LogSetting Tab screens provides a user Header ScreenFeature Settings ChillerSystem Mode Overrides Circuit Mode OverridesDisplay Settings PurgeOperator Interface Operator Interface Operator Interface Operator Interface Operator Interface Interprocessor Communication Inter Processor Communications IPC3IPC3 Definitions Bus Management BindingControl System Components Control panel components layoutControl System Components Control Panel Devices Machine Shutdown Manual Reset MMR Head Relief Request OutputMaximum Capacity Relay Compressor Running RelayRefrigerant Monitor Input 1A17 ExopEpro Enhanced Protection Trmm TRM4 Tracer Comm 4 interfaceCdrp Condenser Refrigerant Pressure Output Temperature based Cdrp Refrigerant Pressure Output Option 1A15Condenser Pressure Output Pressure basedRefrigerant Differential Pressure Indication Output Gbas Generic Building Automation System Percent RLA OutputModule Characteristics External Chilled Water Setpoint EcwsExternal Current Limit Setpoint Wpsr WFC Water Pressure Sensing Option1A14 Communication interface Module 1A8, 1A9, 1A11, 1A12 Quad Relay Output Status1A13, 1A18, 1A19, 1A20 Dual Binary input module Analog Input Recommended Length to Run external Output signals1A15, 1A16, 1A17, 1A21 Dual Analog Input/output Module Unit mounted devices Control System Components Control System Components UCP and Wye-Delta Starter Control Circuits Control Sequence of OperationElectrical Sequence Delay time 200 msec. Opens 2K1 Control Sequence of Operation Control Sequence Operation Test and start timing sequenceAFD Momentary Power Loss MPL Protection Machine Protection Adaptive ControlCurrent Overload Protection Overload trip time versus percent RLAReverse Rotation Protection Phase Loss ProtectionCurrent Limit Protection Minimum and Maximum Capacity Limit Differential to Start or StopSoftLoading Leaving Water Temperature Cutout Evaporator LimitLow Refrigerant Temperature Cutout Head Relief RelayCutout strategy Condenser Limit Restart Inhibit High Vacuum Lockout Oil Temperature Control Controls Chilled Water Reset CWR Outdoor Air TemperatureMaximum Reset Return WaterValues for start reset types Degrees of ResetConstant Return EquationReset Ratio Outdoor air temperature versus degrees of resetReset function for return CWR Reset Ratio = 50% Return CWR Daily Unit Start-Up Unit Start-Up ProceduresUnit Startup Live Electrical Components Toxic HazardsSeasonal Unit Start-Up ModeUnit Shutdown Procedures Unit ShutdownOil Pump Heater Operation Seasonal Unit ShutdownPeriodic Maintenance Daily Maintenance and ChecksMoisture Contamination Record Keeping FormsWeekly Maintenance Normal Chiller Operating CharacteristicsHazardous Voltage w/Capacitors Every 3 MonthsOff-Season Maintenance Annual MaintenanceOil Maintenance Oil Change ProcedureHeater Damage Compressor Oil ChangeOil Filter Replacement Replacing Oil FilterMaintenance Oil Supply System ProblemsOther Maintenance Requirements Hazardous Voltage w/ CapacitorsRotary valve in drain position Front View with Refrigerant PumpContains Refrigerant Refrigerant ChargeRecovery and Recycle Connections Leak TestingCleaning the Condenser Proper Water TreatmentUnit Corrosion Damage Cleaning the EvaporatorControl Settings Adjustments Purge System Unit Preparation103 104 105 106 107 108 109 110 111 112 113 114 115 Trane