Operator
Interface
Chiller
Description | Resolution or (Enumerations), Default | Units |
1. Front Panel Control Type | (Chilled Water, Hot Water), Chilled Water | Enum |
2. Front Panel Chilled Water Setpt | (3) |
|
| + or – XXX.X | Temperature |
3. Front Panel Hot Water Setpt | (3) |
|
| + or – XXX.X | Temperature |
4. Front Panel Current Limit Setpt | XXX (4) | Percent RLA |
5. Front Panel Base Load Cmd | On/Auto | enum |
6. Front Panel Base Load Setpt | XXX | Percent |
7. Front Panel Ice Build Cmd | On/Auto | Enum |
8. Front Panel Ice Termn Setpt | XXX.X | Temperature |
9. Ice to Normal Cool Timer Setpt | Minutes | |
10. Differential to Start | XXX.X | Temperature |
11. Differential to Stop | XXX.X | Temperature |
12. Setpoint Source | *(BAS/Ext/FP, Ext/ Front Panel, Front Panel), |
|
| BAS/Ext/FP Default | Enum |
*Follows hierarchy of selection from left to right (except for ice building which is “OR” logic).
Feature Settings
Description | Resolution or (Enumerations), Default | Units |
1. Chilled Water Reset | (Constant, Outdoor, Return, Disable), Disable | Enum |
2. Return Reset Ratio | XXX | Percent |
3. Return Start Reset | XXX.X | Temperature |
4. Return Maximum Reset | XXX.X | Temperature |
5. Outdoor Reset Ratio | XXX | Percent |
6. Outdoor Start Reset | XXX.X | Temperature |
7. Outdoor Maximum Reset | XXX.X | Temperature |
8. Ext Chilled Water Setpoint | (Enable, Disable), Disable | Enum |
9. Ext Current Limit Setpoint | (Enable, Disable), Disable | Enum |
10. Ice Building Feature Enable | (Enable, Disable), Disable | Enum |
11. Ext Base Loading Setpoint | (Enable, Disable), Disable | Enum |
44 |