Protected Setup Pages

Calibration Page

The Calibration page (FIG. 73) allows you to calibrate the touch panel for accurate button selection.

FIG. 73 Calibration page

1.Press and hold the center button on the navigation wheel for 6 seconds to access the Calibration page (see FIG. 57).

2.Press the crosshairs in turn. If the crosshairs are not touched within ten seconds, the MVP-5200i will return to the Protected Setup page.

3.The page will read "Calibration Successful. Touch to continue." Touch anywhere on the screen to return to the Protected Setup page.

If the screen is not touched at that point, the device will automatically return to the

Protected Setup page within 10 seconds.

Always calibrate the panel before its initial use, and after downloading new firmware.