Using Your AVU1500 with a

Home Automation System (optional)

Report ID

To identify which item the software inquires.

Data

Polling Commands

The frame looks like...

PC UPS (Inquire Input Voltage)

Header

Type

 

Length

 

Report ID

 

 

Data

Check Sum

 

 

 

 

 

 

 

 

 

 

 

 

 

0x7E

0x03

 

0x02

 

0x18

 

 

0x00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS PC (return 120V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Header

Type

Length

Report ID

 

Data

 

Check Sum

 

 

 

 

 

 

 

 

 

 

 

 

0x7E

0x05

0x03

 

0x18

Lo

 

Hi

 

 

 

 

 

 

 

 

 

0xB0

 

0x04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set Commands

The frame looks like...

PC UPS (Set Shutdown Time 60 seconds)

Header

Type

Length

Report ID

 

Data

Check Sum

 

 

 

 

 

 

 

 

0x7E

0x04

0x03

0x15

Lo

 

Hi

 

 

 

 

 

0x3C

 

0x00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UPS PC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Header

Type

Length

Report ID

 

Data

Check Sum

 

 

 

 

 

 

 

 

0x7E

0x02

0x03

0x15

Lo

 

Hi

 

 

 

 

 

0x3C

 

0x00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Belkin PureAV Hybrid AVU1500 UPS

®54

Page 57
Image 57
Belkin AP51300fc10-BLK, AVU1500 user manual Report ID, Data Polling Commands, Set Commands