Using Your AVU1500 with a
Home Automation System (optional)
Power Controls (UsagePage=0x86)
Report ID # | Usage (usage ID) |
| Byte # | Unit | Comment |
|
|
|
|
|
|
16 | }Test | (0x58) | 1 |
| R/W |
|
|
|
|
|
|
17 | }Audible Alarm Control | (0x5A) | 1 |
| R/W |
|
|
|
|
| |
21 | }Delay Before Shutdown (0x57) | 2 | Second | R/W | |
|
|
|
|
|
|
22 | }Delay Before Startup | (0x56) | 2 | Minute | R/W |
|
|
|
|
|
|
65 | }Power On Delay | (0x81) | 1 |
| R/W |
|
|
|
|
|
|
•Test:
•Write value: Test request value
0:No test
1:Quick test
2:Deep test
3:Abort test
•Read value: Test result value
0:No test initiated
1:Done and Passed
2:Done and Warning (no support needed)
3:Done and Error
4:Aborted
5:In progress
• AudibleAlarmControl: | 1: | Disable | 2: | Enable | 3: Muted (Temporarily) |
Read or Write value: | 1: | Disabled | 2: | Enabled | 3: Muted (Temporarily) |
•DelayBeforeShutdown: Writing this value shuts down the UPS after the indicated number of seconds.
•The maximum value is 32767. Setting this object to 0 aborts the countdown. When read, “Delay Before Shutdown” will return the number of seconds remaining until shutdown, or 0 if no shutdown countdown is in effect.
•DelayBeforeStartup: Writing this value starts the output after the indicated number of minutes in “Delay before Startup”. The maximum value is 32767. Sending this command with 0 aborts the countdown.
•PowerOnDelay: Delays the UPS startup after power restores. The power quality may not be stable when power restores; this feature lets the UPS wait a period of time to start up the system.
Belkin PureAV Hybrid AVU1500 UPS