Black Box LES1348A, LES1332A, LES1408A, LES144BA, LES1416A, LES1432A, LES1316A Remote UPS management

Models: LES1116A LES110BA LES1308A LES1348A LES144BA Value-Line and Advanced Console Servers LES114BA LES1432A LES1332A LES1316A LES1416A LES1208A-R2 LES1132A LES1216A-R2 LES1232A LES1248A-R2 LES1408A

1 286
Download 286 pages 6.23 Kb
Page 157
Image 157

Note: These login credentials are not related to the Users and access privileges you configured in Serial

& Networks: Users & Groups.

If you have multiple UPSes and require them to be shut down in a specific order, specify the Shutdown Order for this UPS. This is a whole positive number, or -1. 0s shut down first, then 1s, 2s, etc. -1sare not shut down at all. Defaults to 0.

Select the Driver that you will use to communicate with the UPS. Most console servers are preconfigured so the drop down menu presents a full selection of drivers from the latest Network UPS Tools (NUT version 2.4).

Click New Options in Driver Options if you need to set driver-specific options for your selected NUT driver and hardware combination (more details at http://www.networkupstools.org/doc).

Check Log Status and specify the Log Rate (minutes between samples) if you want the status from this UPS to be logged. You can view these logs from the Status: UPS Status screen.

If you have enabled Nagios services, then you will be presented with an option for Nagios monitoring. Check Enable Nagios to enable this UPS to be monitored using Nagios central management.

Check Enable Shutdown Script if this is the UPS providing power to the console server itself and if a critical power failure occurs, you can perform any "last gasp" actions on the console server before power is lost. Place a custom script in /etc/config/scripts/ups-shutdown(you may use the provided /etc/scripts/ups-shutdownas a template). This script only runs when then UPS reaches critical battery status.

Click Apply.

Note: You can also customize the upsmon, upsd, and upsc settings for this UPS hardware directly from the command line.

8.2.2 Remote UPS management

A Remote UPS is a UPS that is connected as a Managed Device to a remote console server that is monitored (but not managed) by your console server.

You can configure the upsc and upslog clients in the Black Box console server to monitor remote servers that are running Network UPS Tools managing their locally connected UPSes. These remote servers might be other Black Box console servers or generic Linux servers running NUT. You can centrally monitor all these distributed UPSes (which may be spread in a row in a data center, around a campus property, or across the country) through the one central console server window. To add a Remote UPS:

Select the Serial & Network: UPS Connections menu. The Remote UPSes section will display all the remote UPS devices being monitored.

Click Add Remote UPS.

_____________________________________________________________________

724-746-5500 blackbox.com

Page 157

Page 157
Image 157
Black Box LES1348A, LES1332A, LES1408A, LES144BA, LES1416A, LES1432A, LES1316A, LES1308A, LES1232A, LES110BA Remote UPS management