#config -s config.alerts.alert2.signal=[ DSR DCD CTS ]
#config -s config.alerts.alert2.type=signal
Pattern Match Alert
To trigger an alert if the regular expression '.*0.0% id' is found in serial port 10's character stream.
#config -s "config.alerts.alert2.pattern=.*0.0% id"
#config -s config.alerts.alert2.port10=on
#config -s config.alerts.alert2.sensor=temp
#config -s config.alerts.alert2.signal=DSR
#config -s config.alerts.alert2.type=pattern
UPS Power Status Alert
To trigger an alert when myUPS (on localhost) or thatUPS (on remote host 192.168.0.50) power status changes between on line, on battery and low battery.
#config -s config.alerts.alert2.sensor=temp
#config -s config.alerts.alert2.signal=DSR
#config -s config.alerts.alert2.type=ups
#config -s config.alerts.alert2.ups1=myUPS@localhost
#config -s config.alerts.alert2.ups2=thatUPS@192.168.0.50
Environmental and Power Sensor Alert
#config -s config.alerts.alert2.enviro.high.critical='critical value'
#config -s config.alerts.alert2.enviro.high.warning='warning value'
#config -s config.alerts.alert2.enviro.hysteresis='value'
#config -s config.alerts.alert2.enviro.low.critical='critical value'
#config -s config.alerts.alert2.enviro.low.warning='warning value'
#config -s config.alerts.alert2.enviro1='Enviro sensor name'
#config -s config.alerts.alert2.outlet#='RPCname'.outlet#
'alert2.outlet#' increments sequentially with each added outlet. The second 'outlet#' refers to the specific RPC power outlets.
#config -s config.alerts.alert2.rpc#='RPC name'
#config -s config.alerts.alert2.sensor=[ temp humid load charge]
#config -s config.alerts.alert2.signal=DSR
#config -s config.alerts.alert2.type=enviro
#config -s config.alerts.alert2.ups1='UPSname@hostname'
Example1: To configure a temperature sensor alert for a sensor called 'SensorInRoom42':
#config -s config.alerts.alert2.sensor=temp
#config -s config.alerts.alert2.enviro.high.critical=60
#config -s config.alerts.alert2.enviro.high.warning=50
#config -s config.alerts.alert2.enviro.hysteresis=2
#config -s config.alerts.alert2.enviro.low.critical=5
#config -s config.alerts.alert2.enviro.low.warning=10
#config -s config.alerts.alert2.enviro1=SensorInRoom42
#config -s config.alerts.alert2.signal=DSR
#config -s config.alerts.alert2.type=enviro
Example2: To configure a load sensor alert for outlets 2 and 4 for an RPC called 'RPCInRoom20':
#config -s config.alerts.alert2.outlet1='RPCname'.outlet2
#config -s config.alerts.alert2.outlet2='RPCname'.outlet4