#config -s config.alerts.alert2.signal=[ DSR DCD CTS ]

#config -s config.alerts.alert2.type=signal

Pattern Match Alert

To trigger an alert if the regular expression '.*0.0% id' is found in serial port 10's character stream.

#config -s "config.alerts.alert2.pattern=.*0.0% id"

#config -s config.alerts.alert2.port10=on

#config -s config.alerts.alert2.sensor=temp

#config -s config.alerts.alert2.signal=DSR

#config -s config.alerts.alert2.type=pattern

UPS Power Status Alert

To trigger an alert when myUPS (on localhost) or thatUPS (on remote host 192.168.0.50) power status changes between on line, on battery and low battery.

#config -s config.alerts.alert2.sensor=temp

#config -s config.alerts.alert2.signal=DSR

#config -s config.alerts.alert2.type=ups

#config -s config.alerts.alert2.ups1=myUPS@localhost

#config -s config.alerts.alert2.ups2=thatUPS@192.168.0.50

Environmental and Power Sensor Alert

#config -s config.alerts.alert2.enviro.high.critical='critical value'

#config -s config.alerts.alert2.enviro.high.warning='warning value'

#config -s config.alerts.alert2.enviro.hysteresis='value'

#config -s config.alerts.alert2.enviro.low.critical='critical value'

#config -s config.alerts.alert2.enviro.low.warning='warning value'

#config -s config.alerts.alert2.enviro1='Enviro sensor name'

#config -s config.alerts.alert2.outlet#='RPCname'.outlet#

'alert2.outlet#' increments sequentially with each added outlet. The second 'outlet#' refers to the specific RPC power outlets.

#config -s config.alerts.alert2.rpc#='RPC name'

#config -s config.alerts.alert2.sensor=[ temp humid load charge]

#config -s config.alerts.alert2.signal=DSR

#config -s config.alerts.alert2.type=enviro

#config -s config.alerts.alert2.ups1='UPSname@hostname'

Example1: To configure a temperature sensor alert for a sensor called 'SensorInRoom42':

#config -s config.alerts.alert2.sensor=temp

#config -s config.alerts.alert2.enviro.high.critical=60

#config -s config.alerts.alert2.enviro.high.warning=50

#config -s config.alerts.alert2.enviro.hysteresis=2

#config -s config.alerts.alert2.enviro.low.critical=5

#config -s config.alerts.alert2.enviro.low.warning=10

#config -s config.alerts.alert2.enviro1=SensorInRoom42

#config -s config.alerts.alert2.signal=DSR

#config -s config.alerts.alert2.type=enviro

Example2: To configure a load sensor alert for outlets 2 and 4 for an RPC called 'RPCInRoom20':

#config -s config.alerts.alert2.outlet1='RPCname'.outlet2

#config -s config.alerts.alert2.outlet2='RPCname'.outlet4