Logging

Enabled

Log interval

600 second

Number of power outlets

4 (depends on the type/model of the RPC)

#config -s config.ports.port2.power.type=APC 7900

#config -s config.ports.port2.power.name=MyRPC

#config -s "config.ports.port2.power.description=RPC in room 5"

#config -s config.ports.port2.power.username=rpclogin

#config -s config.ports.port2.power.password=secret

#config -s config.ports.port2.power.snmp.community=v1

#config -s config.ports.port2.power.log.enabled=on

#config -s config.ports.port2.power.log.interval=600

#config -s config.ports.port2.power.outlets=4

The following five commands are used by the Management Console to add the RPC to “Managed Devices”:

#config -s config.devices.device3.connections.connection1.name=myRPC

#config -s "config.devices.device3.connections.connection1.type=RPC Unit"

#config -s config.devices.device3.name=myRPC

#config -s "config.devices.device3.description=RPC in room 5"

#config -s config.devices.total=3

The following command will synchronize the live system with the new configuration:

# config -a

14.11Environmental

To configure an environmental monitor with the following details:

Monitor name

Envi4

Monitor Description

Monitor in room 5

Temperature offset

2

Humidity offset

5

Enable alarm 1 ?

yes

Alarm 1 label

door alarm

Enable alarm 2 ?

yes

Alarm 2 label

window alarm

Logging enabled ?

yes

Log interval

120 seconds

#config -s config.ports.port3.enviro.name=Envi4

#config -s "config.ports.port3.enviro.description=Monitor in room 5"

#config -s config.ports.port3.enviro.offsets.temp=2

#config -s config.ports.port3.enviro.offsets.humid=5

#config -s config.ports.port3.enviro.alarms.alarm1.alarmstate=on

#config -s config.ports.port3.enviro.alarms.alarm1.label=door alarm

#config -s config.ports.port3.enviro.alarms.alarm2.alarmstate=on

#config -s config.ports.port3.enviro.alarms.alarm2.label=window alarm

#config -s config.ports.port3.enviro.alarms.total=2

#config -s config.ports.port3.enviro.log.enabled=on

#config -s config.ports.port3.enviro.log.interval=120

Assign alarms.total=2 even if they are off.

The following 5 commands will add the environmental monitor to “Managed devices”: