D1260/D1260B Owner's Manual Part III: Advanced Commands - FIRE TEST ? (COMMAND + 5 + 8)
4.The current state of the area is displayed for 3 seconds before returning to idle text.
FIRE TEST ? (COMMAND + 5 + 8)
Use this function to test fire points and other
Upon initiation, the fire test will test the fire bell pattern on the bell output and ring the command center fire bell for 2 seconds. The AC will be disabled for 4 minutes in order to test the system’s battery power. If the battery cannot maintain the system for the
If there is no activity on the system for 20 minutes, the system will automatically exit from the Fire Test.
Using Fire Test:
1.Ensure your keypad shows idle disarmed text.
2.Press the COMMAND key. The display shows *System Command*.
3.Press the 5 key and then the 8 key.
If you prefer, you may use the Command Menu in place of steps 2 and 3 to initiate this function.
Press the MENU> soft key to enter the
Command Menu.
Press NEXT> soft key repeatedly.
When you reach the FIRE TEST ?> prompt, press its adjacent soft key.
4.When the display shows ### points remain to be tested you can begin. (### is the number of points).
Test each point by first activating the detection device to fault the point.
If you know the point number, you can enter it by pressing its number key and then the ENTER key.
The display will change to show the point that was entered. If the point is invalid the message “Invalid Point” or “This is not a valid walk point” appears.