D1260/D1260B Owner's Manual Part III: Advanced Commands - DISPLAY REV ? (COMMAND + 5 + 9)
5.As you fault each point, your command center will display the point text for 60 seconds and ring the fire sounders for 2 seconds. This verifies that the detection device is working properly. Your system automatically resets smoke detectors.
•When a resettable point (such as a smoke detector) is faulted, the display shows Sensors…resetting…please wait… for 5 seconds. During this time power is removed from smoke power relays.
•Faulting a point more than once does not increment the test count. However, the command center emits a brief tone and displays the point text each time you fault the point allowing you to test multiple devices assigned to one point.
6.When the point has been tested, the display changes to show SMOKE DETECTOR tested.
7.During the Fire Test you may want to see the points that remain untested by pressing the View untested pts> soft key.
The display shows ### pts untested.
Press the Point information> soft key to see information about specific points that have not yet been tested.
The display changes to show the information for that point.
Move through this list by pressing the Next Point> soft key.
Press the <Exit soft key to return to the ###
points remain to be tested. before continuing the Fire Test.
8.When all
Press the <Exit soft key.
The display momentarily shows All points have been tested.
before returning to idle text.