7.4.3 Thermal Control

The Galaxy 65 Enclosure uses extensive thermal monitoring and takes a number of actions to ensure component temperatures are kept low and also to minimize acoustic noise.Air flow is from front to rear of the enclosure.

Symptom

Cause

 

Action

 

 

 

 

If the ambient air is cool

The first stage in the thermal

1

Check the installation for any airflow

(below 25 °C) and the fans

control process is for the fans

 

restrictions at either the front or rear

are observed to increase in

to automatically increase in

 

of the enclosure. A minimum gap of

speed then some restriction

speed when a thermal

 

25mm at the front and 50mm at the

on airflow may be causing

threshold is reached. This

 

rear is recommended.

additional internal

may be caused by higher

 

 

temperature rise.

ambient temperatures in the

2

Check for restrictions due to dust

 

local environment and may

 

build-up, clean as appropriate.

Note: This is not a fault

be perfectly normal.

3

Check for excessive re-circulation of

condition.

 

 

Note: This threshold

 

heated air from rear to the front, use

 

changes according to the

 

in a fully enclosed rack installation is

 

number of drives and power

 

not recommended.

 

supplies fitted.

4

Check that all Blank modules are in

 

 

 

 

 

place.

 

 

5

Reduce the ambient temperature.

 

 

 

 