CHAPTER 4: COMMUNICATION INSTALLATION

4.3: Network of Instruments and Long Distance Communication

The RS-485 Transceiver is required for a large network of instruments.

In a two-wire connection, a maximum of 900 instruments can be included in the same network (Figure 4.7)

In a four-wire connection, a maximum of 3600 instruments can be included in the same network (Figure 4.8).

 

 

 

RS-485

 

DEVICE

32 UNITS

DEVICE

TRANSCEIVER

 

 

 

 

(Acts as Repeater)

 

 

 

 

32

COMPUTER

 

 

 

TRANSCEIVERS

 

 

 

 

 

 

 

RS-485

 

DEVICE

32 UNITS

DEVICE

TRANSCEIVER

 

 

 

 

(Acts as Repeater)

 

Figure 4.7: 2-Wire RS-485 Communication Installation Connection with Transceiver

DEVICE

32 UNITS

DEVICE

RS-485

 

TRANSCEIVER

 

 

 

 

(Acts as Repeater)

 

 

 

 

32

COMPUTER

 

 

 

TRANSCEIVERS

 

 

 

 

DEVICE

32 UNITS

DEVICE

RS-485

 

TRANSCEIVER

 

 

 

 

(Acts as Repeater)

 

Figure 4.8: 4-Wire RS-485 Communication Installation Connection with Transceiver

Use modems (dedicated or dial-up) when the instruments are located at great distances. However, set the modem to auto answer at the recommended value of 1200 baud rate, if noise conditions exist. Also, flow control must be disabled.

GE Multilin

EPM 5000 series Advanced Power Meters

23

Page 27
Image 27