CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

PACK

SWITCH

FEATURE

SEGMENT POSITION

 

A

Reserved

0

B

Reserved

C

Reserved

 

D

Phase Reversal Limit Detection

UP: Enable

 

 

 

DOWN: Disable

 

A

Non-significant will blank leading zero

UP: Enable

 

 

 

DOWN: Disable

1

B

Reset Protection

UP: Enable

 

(see Part I: Installation and Operation)

DOWN: Disable

 

C

Phase Reversal Rotation Selection

UP: CBA Rotation

 

 

 

DOWN: ABC Rotation

 

D

Open Delta Installation

UP: Enable

 

 

(see Part I: Installation and Operation)

DOWN: Disable

 

A

Limit/Relay Control

UP: Average

 

 

 

DOWN: Instantaneous

2

B

Power Factor Polarity Indicates + (voltage referenced)

UP: -PF

 

or

DOWN: +PF

 

 

- (current referenced)

 

 

C, D

For EI-BUS protocol: Switch C is DOWN, Switch D is DOWN.

 

 

For MODBUS protocol, ASCII framing: Switch C is UP, Switch D is UP.

 

 

For MODBUS protocol, RTU framing: Switch C is DOWN Switch D is UP.

 

 

For DNP 3.0 protocol: Switch C is UP, Switch D is DOWN.

 

A

Trip Relay Computer Control 1

UP: Enable

 

 

(Relay Control 1 and 2 apply only if Relay Option -NL

DOWN: Disable

3

 

was ordered.)

 

B

Trip Relay Computer Control 2

UP: Enable

 

 

(Relay Control 1 and 2 apply only if Relay Option -NL

DOWN: Disable

 

 

was ordered.)

 

 

C

RS-232 or RS-485 Communications or Print

UP: Enable Communications

 

 

 

DOWN: Enable DC Output

 

D

DC Output

UP: Enable DC Output or Print

 

 

(To operate DC Output, disable PACK 3, Switch C)

Communication

 

 

or

 

 

 

Print Operating and Programming Data

DOWN: Disable DC Output and

 

 

(To print, set PACK 3 Switches C and D to UP

Print

 

 

position.)

 

Table 9-2: System Configuration—Switch Packs for Group 0, Function 3

GE Multilin

EPM 5000 series Advanced Power Meters

47

Page 51
Image 51
GE EPM 5200, EPM 5300, EPM 5350 instruction manual Pack Switch Feature Segment Position, Down +PF