GE EPM 5350, EPM 5200, EPM 5300 CHAPTER PROGRAMMING GROUP 0 - GLOBAL METER SETUP, Function, Number

Models: EPM 5300 EPM 5200 EPM 5350

1 100
Download 100 pages 46.61 Kb
Page 47
Image 47
CHAPTER 9

CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

CHAPTER 9

PROGRAMMING GROUP 0 – GLOBAL METER SETUP

The Global Meter Setup includes FUNCTIONS 0 through 7 that control configuration and basic operation. FUNCTION 3 System Configuration contains Switch PACKS with various options, including Open Delta installation, communications or DC Output setup. Global Meter Setup is the section in which general features are programmed.

FUNCTION

Function

NUMBER

 

0.

Integration Interval

1.

Meter Address for Communication

2.

Baud Rate for Communication

3.

System Configuration (see Table 9-2)

4.

Relay 1 Set-up / Time delay

5.

Relay 2 Set-up / Time delay

6.

KYZ Parameter Selection

7.

Number of Phases

E.

Exit Programming GROUP 0

Table 9-1: Group 0 Programming Format

9.1: Group 0, Function 0—The Integration Interval

INTEGRATION INTERVAL: Time which all instantaneous readings are averaged to obtain a max and

min demand. The Integration Interval is entered in seconds. When entering 15 minutes, enter: 0900 seconds. The default value is 900 seconds.

To change the Integration Interval:

NOTE: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 1:

a. Enter Group Level of Programming Mode (see Chp. 8).

b. Press MAX/MIN/LIMITS until 0. appears in upper display.

c. Press AMPS to activate the Group.

 

MAX

 

 

 

 

 

 

 

 

 

 

 

AC VOLTS

 

 

 

 

 

 

 

 

 

 

 

 

A B C A B C

 

MIN

 

 

 

 

 

 

 

 

 

 

 

N N N B C A

 

LM1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LM2

 

 

 

 

 

 

 

 

 

 

 

 

 

AC AMPS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B C N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVA

 

 

 

 

KVAH

 

 

 

KWH

 

 

FREQ

 

 

KVAR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX/MIN

 

VOLTS

 

 

 

AMPS

 

 

POWER

 

 

PHASE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIMITS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEXT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

!Function 00. appears in upper display. The second 0 indicates Function 0

!Lower display indicates current Interval setting.

GE Industrial Systems

5300P Advanced Power Meter

43

Page 47
Image 47
GE EPM 5350 CHAPTER PROGRAMMING GROUP 0 - GLOBAL METER SETUP, Group 0, Function 0-The Integration Interval, Number