CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

9.10: Group 0, Function 7—Number of Phases

NOTE: ENTER 1 FOR SINGLE PHASE/SINGLE WIRE.

ENTER 2 FOR SINGLE PHASE/TWO WIRE.

ENTER 3 FOR THREE PHASE/THREE OR FOUR WIRE.

*STANDARD FACTORY SET-UP IS THREE-PHASE FOUR-WIRE

Note: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

MAX

AC VOLTS

A B C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

A B C N

 

POWER

 

 

 

PF

 

 

 

KW

 

 

 

KVA

KVAH

KWH

FREQ

KVAR

MAX/MIN

VOLTS AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 1:

a. Enter Group Level of Programming Mode. (Chapter 8)

b. Press MAX/MIN/LIMITS if 0. does not appear.

c. Press AMPS to activate the Group.

MAX

 

 

AC VOLTS

 

 

A

B C A B C

MIN

 

 

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 2:

!00. appears in upper display.

a. Press MAX/MIN/LIMITS until 07 appears in upper display.

b. Press AMPS to activate the Group.

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 3:

a. Press VOLTS to select numbers 1, 2 or 3.

b. Press AMPS to store.

See Chapter 14 to Exit.

58

EPM 5000 series Advanced Power Meters

GE Multilin

Page 62
Image 62
GE EPM 5350, EPM 5200, EPM 5300 Group 0, Function 7-Number of Phases, Standard Factory SET-UP is THREE-PHASE FOUR-WIRE