CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

To change the Relay Mode to either Fail-safe or Reset:

NOTE: Press MAX/MIN/LIMITS at any time to cancel before storing the last digit or switch.

MAX

AC VOLTS

A B C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

A B C N

 

POWER

PF

KW

KVA

KVAH

 

KWH

 

FREQ

 

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 1:

a. Enter Group Level of Programming Mode (see Chp. 8).

b. Press MAX/MIN/LIMITS until 0. appears in upper display.

c. Press AMPS to activate the Group.

MAX

AC VOLTS

A B C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

A B C N

 

POWER

PF

KW

KVA

KVAH

 

KWH

 

FREQ

 

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 2:

a.Press MAX/MIN/LIMITS until 04.P (for Relay 1) or 05.P (for Relay 2) appears in upper display.

!Lower display indicates current setting.

MAX

AC VOLTS

A B C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

A B C N

 

POWER

PF

KW

KVA

KVAH

 

KWH

 

FREQ

 

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 3:

a.Press AMPS to begin Data Entry Sequence.

!The previous setting shifts to middle display and four dashes appear in lower display.

b. Press VOLTS for desired switch position.

c. Press AMPS to store each setting.

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

!Repeat this procedure until new switch setting is entered.

!When complete, middle display blanks and lower display indicates the programming.

See Chapter 14 to Exit.

52

EPM 5000 series Advanced Power Meters

GE Multilin

Page 56
Image 56
GE EPM 5350, EPM 5200, EPM 5300 instruction manual To change the Relay Mode to either Fail-safe or Reset