a. Press MAX/MIN/LIMITS until Function 04.P appears

CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP

To change Time Delays:

NOTE: Press MAX/MIN/LIMITS at any time, to cancel before storing the last digit or Switch.

MAX

AC VOLTS

A B C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

A B C N

 

POWER

 

 

 

PF

 

 

 

KW

 

 

 

KVA

KVAH

KWH

FREQ

KVAR

MAX/MIN

VOLTS AMPS

POWER

PHASE

LIMITS

 

NEXT

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 1:

Step 2:

a. Enter Group Level of Programming Mode

To program Relay 1:

(see Chp. 8).

a. Press MAX/MIN/LIMITS until Function 04.P appears

b. Press MAX/MIN/LIMITS until 0. appears in upper

in upper display.

display.

To program Relay 2 and 3:

c. Press AMPS to activate the Group.

a. Press MAX/MIN/LIMITS until Function 05.P appears.

 

 

b. Press VOLTS once to display 04.0 (On to Off delay

 

time).

 

c. Press VOLTS twice to display 04.1 (Off to On delay

 

time).

 

! Lower display indicates current Time Delays.

MAX

AC VOLTS

A B C A B C

MIN

N N N B C A

LM1

 

LM2

AC AMPS

 

 

A B C N

 

POWER

 

 

 

PF

 

 

 

KW

 

 

 

KVA

KVAH

KWH

FREQ

KVAR

MAX/MIN

VOLTS AMPS

POWER

PHASE

LIMITS

 

NEXT

Step 3:

a.Press AMPS to begin Data Entry Sequence.

!The previous value shifts to middle display and four dashes appear in lower display.

b. Press VOLTS until number appears.

c. Press AMPS to store each number.

MAX

 

 

AC VOLTS

 

 

A B C A B C

MIN

 

 

N N N B C A

LM1

 

 

 

 

 

 

LM2

 

 

AC AMPS

 

 

 

 

 

 

 

A B C N

 

 

 

 

POWER

 

 

 

 

PF

 

 

 

 

KW

 

 

 

 

KVA

KVAH

KWH

 

FREQ

KVAR

MAX/MIN

VOLTS

AMPS

POWER

PHASE

LIMITS

 

NEXT

!Repeat this procedure until new Time Delay is entered.

!When complete, middle display blanks and lower display

Indicates the new Time Delay.

See Chapter 14 to Exit.

54